Global (English)
Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Preventa safety remote mixed I/O module - 20 I not isolated - 8 O not isolated

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Preventa safety remote mixed I/O module
    safety module name
    XPSMF3
    safety module application
    Extension of I/O capacity
    safety use category
    Category 4 maximum conforming to EN 954-1
    Performance level e conforming to EN/ISO 13849-1
    SIL 3 conforming to EN/IEC 61508
    function of module
    Monitoring safety actuators discrete input
    Monitoring safety actuators discrete output
    Monitoring safety detection discrete input
    Monitoring safety dialogue discrete input
    [Us] rated supply voltage
    24 V DC (- 15...20 %)
    supply
    SELV or PELV conforming to EN/IEC 60950
    discrete input number
    20, not isolated
    discrete output number
    8, not isolated
    structure type
    10BASE-T/100BASE-TX
    Complementary
    response time
    Depending on size of application
    voltage state 0 guaranteed
    <= 5 V for discrete input
    voltage state 1 guaranteed
    15...< 30 V for discrete input
    current state 0 guaranteed
    1.25...1.5 mA, discrete input
    current state 1 guaranteed
    <= 2 mA, discrete input
    discrete input voltage
    20 V
    discrete input current
    100 mA
    input protection type
    Protected against short-circuit
    switching voltage
    7.5 V for discrete input
    discrete output voltage
    24 V DC
    output voltage tolerance
    +/- 2 %
    discrete output current
    <= 7 A (all channels)
    1 A at 60 °C (channels 4 and 8)
    2 A at 50 °C (channels 4 and 8)
    0.5 A at 60 °C (channels 1 to 3 and 5 to 7)
    minimum load
    2 mA per channel
    leakage current
    <= 1 mA, at 2 V at state 0 for discrete output
    communication port protocol
    Safe Ethernet with 2 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better
    exchange mode
    Half duplex, full duplex, autonegotiation
    number of terminal blocks
    1 for power supply
    2 for discrete input
    2 for discrete output
    current consumption
    8 A at 24 V DC on power supply
    mounting support
    35 mm symmetrical DIN rail
    depth
    66.5 mm
    height
    109 mm
    width
    207 mm
    product weight
    1 kg
    Environment
    IP degree of protection
    IP20
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • French
    • Italian
    • German
    Catalogue
    Date
    Size
    Add to My Documents
    Safety remote I/O modules XPSMF1/2/3, for Preventa safety PLCs XPSMF (Version 1.0)
    Modules d’E/S de sécurité distantes Type XPSMF1/2/3, pour automates de sécurité Preventa XPSMF (Version 1.0)
    User guide
    Date
    Size
    Add to My Documents
    XPSMF3DIO20802 Dezentrales Sicherheits-E/A-Modul, Handbuch zur Hardware (Version 01)
    XPSMFWIN Manuale del software (Version 02)
    Date 6/30/07
    Size 4.2 MB
    XPSMF3DIO20802 Module E/S de sécurité distant, Manuel du matériel (Version 01)
    XPSMFWIN Manual de software (Version 02)
    Date 6/30/07
    Size 4.2 MB
    XPSMF3DIO20802 Safety Remote I/O Module, Hardware Manual (Version 01)
    XPSMF3DIO20802 Módulo I/O Remoto de Segurança, Manual do Hardware (Version 01)
    Safety Suite V2, Consignes d'installation (Version 03)
    XPSMFWIN Software-Handbuch (Version 02)
    Date 6/30/07
    Size 5 MB
    XPSMFWIN Manual de Software (Version 02)
    Date 6/30/07
    Size 4.2 MB
    XPSMF3DIO20802 Módulo de E/S remota de seguridad, Manual del hardware (Version 01)
    XPSMFWIN Manuel logiciel (Version 02)
    Date 6/30/07
    Size 5.1 MB
    XPSMF3DIO20802 Modulo I/O di sicurezza remoto, Manuale hardware (Version 01)
    Certificate
    Date
    Size
    Add to My Documents
    UL E486184 - NRAQ-NRAQ7 (Version 1.0)
    Date 12/12/18
    Size 395.6 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /