Global (English)

Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric XPSATR1153C Image

View all Preventa XPS

Preventa XPS - XPSATR1153C

Emergency Stop

Schneider Electric XPSATR1153C Image
View all Preventa XPS
Preventa XPS - XPSATR1153C
Emergency Stop

module XPSATR - Emergency stop and protective guard - 24V DC, time delay 3s

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Preventa safety module
    safety module name
    XPSATR
    safety module application
    For emergency stop and protective guard applications
    function of module
    Emergency stop monitoring 1-channel wiring
    Emergency stop monitoring 2-channel wiring
    Protective guard monitoring
    safety level
    Can reach SILCL 3 conforming to EN/IEC 62061 time delay safety outputs
    Can reach PL e/category 4 conforming to EN/ISO 13849-1 instantaneous safety outputs
    safety reliability data
    MTTFd = 85 years conforming to EN/ISO 13849-1
    PFHd = 2E-9 1/h conforming to EN/IEC 62061
    DC > 99 % conforming to EN/ISO 13849-1
    type of start
    Automatic
    Manual
    connections - terminals
    Cage clamp terminals, removable terminal block
    Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm² flexible cable with cable end, with bezel
    Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm² flexible cable with cable end, without bezel
    Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm² solid or flexible cable without cable end
    Cage clamp terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1 mm² flexible cable with cable end, with bezel
    output type
    Relay instantaneous opening 3 NO, volt-free
    Relay time delay opening 3 NO, volt-free
    number of additional circuits
    1 NC
    [Us] rated supply voltage
    24 V DC (- 15...10 %)
    Complementary
    synchronisation time between inputs
    1 s
    power consumption in W
    2.8 W DC
    input protection type
    Internal, electronic
    time delay range
    0.1...3 s
    [Uc] control circuit voltage
    24 V DC
    breaking capacity
    3 A at 24 V (DC-13) for relay output
    output thermal current
    6 A for instantaneous and time delay outputs
    [Ith] conventional free air thermal current
    8 A
    associated fuse rating
    6 A fuse type gG for instantaneous and time delay outputs conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
    minimum output current
    10 mA for relay output
    minimum output voltage
    17 V for relay output
    response time on input open
    <= 20 ms
    [Ui] rated insulation voltage
    300 V
    [Uimp] rated impulse withstand voltage
    4 kV overvoltage category III conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
    local signalling
    5 LEDs
    mounting support
    35 mm symmetrical DIN rail
    product weight
    0.33 kg
    Environment
    standards
    EN 60204-1
    EN/IEC 60947-5-1
    EN/IEC 61496-1
    EN/ISO 13849-1
    EN 62061
    EN 50156-1
    product certifications
    CSA
    TÜV
    UL
    IP degree of protection
    IP20 (terminals) conforming to EN/IEC 60529
    IP40 (enclosure) conforming to EN/IEC 60529
    ambient air temperature for operation
    -25...55 °C
    ambient air temperature for storage
    -25...75 °C
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    Certificate
    Date
    Size
    Add to My Documents
    Date 11/19/18
    Size 614 KB
    Date 9/28/18
    Size 7.4 MB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 6/19/18
    Size 530.8 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Product environmental
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions