Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric XPSAR311144P Image

View all Preventa XPS

Preventa XPS - XPSAR311144P

Emergency Stop

Schneider Electric XPSAR311144P Image
View all Preventa XPS
Preventa XPS - XPSAR311144P
Emergency Stop

module XPSAR - Emergency stop - 24 V AC DC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Preventa safety module
    safety module name
    XPSAR
    safety module application
    For emergency stop, switch and safety light curtain monitoring
    function of module
    Monitoring of electro-sensitive protection equipment (ESPE)
    Monitoring of a movable guard associated with 2 switches and automatic start
    Monitoring of a movable guard
    Emergency stop monitoring 1-channel wiring
    Emergency stop with 2 NC contacts monitoring 2-channel wiring
    Multiple emergency stop monitoring 2-channel wiring
    safety level
    Can reach PL e/category 4 conforming to EN/ISO 13849-1
    Can reach SILCL 3 conforming to EN/IEC 62061
    safety reliability data
    DC > 99 % conforming to EN/ISO 13849-1
    MTTFd = 277.8 years conforming to EN/ISO 13849-1
    PFHd = 2.22E-9 1/h conforming to EN/IEC 62061
    type of start
    Configurable
    connections - terminals
    Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1.5 mm² flexible cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm² flexible cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm² solid cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm² flexible cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1 mm² solid cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1.5 mm² flexible cable with cable end, with double bezel
    Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.25...2 x 1 mm² flexible cable with cable end, with double bezel
    output type
    Relay instantaneous opening 7 NO, volt-free
    number of additional circuits
    2 NC + 4 solid state outputs
    [Us] rated supply voltage
    24 V AC (- 15...10 %)
    24 V DC (- 15...10 %)
    Complementary
    synchronisation time between inputs
    100 ms
    supply frequency
    50/60 Hz
    power consumption in W
    <= 4 W DC
    power consumption in VA
    <= 7 VA AC
    input protection type
    Internal, electronic
    [Uc] control circuit voltage
    24 V DC
    line resistance
    50 Ohm
    breaking capacity
    C300 : 360 VA, AC-15 (holding) for relay output
    C300 : 3600 VA, AC-15 (inrush) for relay output
    breaking capacity
    20 mA at 24 V
    2 A at 24 V (DC-13) time constant: 50 ms for relay output
    output thermal current
    10 A per relay for relay output
    [Ith] conventional free air thermal current
    40 A
    associated fuse rating
    10 A fuse type fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
    6 A fuse type gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
    minimum output current
    170 mA for relay output
    minimum output voltage
    17 V for relay output
    response time on input open
    <= 20 ms
    [Ui] rated insulation voltage
    300 V (degree of pollution: 2) conforming to DIN VDE 0110 part 1
    300 V (degree of pollution: 2) conforming to IEC 60947-5-1
    [Uimp] rated impulse withstand voltage
    4 kV overvoltage category III conforming to IEC 60947-5-1
    4 kV overvoltage category III conforming to DIN VDE 0110 part 1
    local signalling
    4 LEDs
    current consumption
    30 mA at 24 V DC (on power supply)
    mounting support
    35 mm symmetrical DIN rail
    product weight
    0.3 kg
    Environment
    standards
    EN 1088/ISO 14119
    EN/IEC 60204-1
    EN/IEC 60947-5-1
    EN/ISO 13850
    product certifications
    CSA
    TÜV
    UL
    IP degree of protection
    IP20 (terminals) conforming to EN/IEC 60529
    IP40 (enclosure) conforming to EN/IEC 60529
    ambient air temperature for operation
    -10...55 °C
    ambient air temperature for storage
    -25...85 °C
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • French
    • Italian
    • German
    Certificate
    Date
    Size
    Add to My Documents
    Date 10/18/12
    Size 1.4 MB
    Date 8/7/15
    Size 1.6 MB
    Date 5/4/18
    Size 1.2 MB
    Date 10/29/18
    Size 322 B
    Instruction sheet
    Date
    Size
    Add to My Documents
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 6/19/18
    Size 541.3 KB
    Product environmental
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions