Global (English)
Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all Modicon Premium
Schneider Electric TSXDSY08R5AC Image

TSXDSY08R5AC

Schneider Electric TSXDSY08R5AC Image
TSXDSY08R5AC

discrete output module - 8 relay protected output - 24..240V AC - 5 A

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Modicon Premium Automation platform
    product or component type
    Discrete output module
    discrete output number
    8
    discrete output type
    Relay protected
    discrete output voltage
    24...240 V AC conforming to EN/IEC 61131-2 20...264 V
    24...48 V DC conforming to EN/IEC 61131-2 19...60 V
    Complementary
    [Ith] conventional free air thermal current
    5 A
    response time
    < 10 ms activation
    < 15 ms deactivation
    contacts type and composition
    2 x 2 C/O + 2 x 2 NO
    output overvoltage protection
    RC circuit and Ge-Mov
    output overload protection
    6.3 A, interchangeable fuse per common fast blow
    short-circuit protection
    6.3 A, interchangeable fuse per common fast blow
    isalotion resistance
    > 10 MOhm 500 V
    power dissipation
    (0.25 W + 0.24 W x No of outputs at state 1)
    electrical durability
    1000000 cycles DC-12 24 W 24 V resistive
    1000000 cycles DC-12 50 W 48 V resistive
    1000000 cycles DC-3 24 W 24 V inductive
    1000000 cycles DC-3 50 W 48 V inductive
    2000000 cycles DC-3 10 W 24 V inductive
    2000000 cycles DC-3 24 W 48 V inductive
    300000 cycles DC-12 100 W 48 V resistive
    300000 cycles DC-12 50 W 24 V resistive
    1000000 cycles AC-12 100 VA 48 V resistive
    2000000 cycles AC-14 50 VA 48 V inductive
    2000000 cycles AC-15 50 VA 48 V inductive
    500000 cycles AC-12 200 VA 48 V resistive
    500000 cycles AC-14 50 VA 24 V inductive
    500000 cycles AC-15 50 VA 24 V inductive
    5000000 cycles AC-14 20 VA 48 V inductive
    5000000 cycles AC-15 20 VA 48 V inductive
    700000 cycles AC-12 100 VA 24 V resistive
    100000 cycles AC-14 440 VA 220...240 V inductive
    100000 cycles AC-15 440 VA 220...240 V inductive
    1000000 cycles AC-12 220 VA 100...120 V resistive
    1000000 cycles AC-12 440 VA 220...240 V resistive
    1000000 cycles AC-14 220 VA 220...240 V inductive
    1000000 cycles AC-15 220 VA 220...240 V inductive
    10000000 cycles AC-14 20 VA 100...120 V inductive
    10000000 cycles AC-14 20 VA 220...240 V inductive
    10000000 cycles AC-15 20 VA 100...120 V inductive
    10000000 cycles AC-15 20 VA 220...240 V inductive
    150000 cycles AC-14 220 VA 100...120 V inductive
    150000 cycles AC-15 220 VA 100...120 V inductive
    1500000 cycles AC-14 110 VA 100...120 V inductive
    1500000 cycles AC-15 110 VA 100...120 V inductive
    3000000 cycles AC-14 110 VA 220...240 V inductive
    3000000 cycles AC-15 110 VA 220...240 V inductive
    500000 cycles AC-12 440 VA 100...120 V resistive
    marking
    CE
    electrical connection
    Screw terminal block
    current consumption
    55 mA 5 V DC
    80 mA 24 V DC rack
    module format
    Standard
    product weight
    0.42 kg
    Environment
    dielectric strength
    2000 V 50/60 Hz 60 s
    standards
    73/23/EEC
    89/336/EEC
    92/31/EEC
    93/68/EEC
    CSA C22.2 No 142
    IEC 61131-2
    UL 508
    CSA C22.2 No 213 Class I Division 2 Group A
    CSA C22.2 No 213 Class I Division 2 Group B
    CSA C22.2 No 213 Class I Division 2 Group C
    CSA C22.2 No 213 Class I Division 2 Group D
    product certifications
    ABS
    BV
    DNV
    GL
    LR
    RINA
    RMRS
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -25...70 °C
    relative humidity
    10...95 % without condensation for operation
    5...95 % without condensation for storage
    operating altitude
    0...2000 m
    protective treatment
    Conformal coating Humiseal 1A33
    TC
    IP degree of protection
    IP20
    pollution degree
    2
    Offer Sustainability
    RoHS (date code: YYWW)
    Compliant  - since  0908  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    User guide
    Date
    Size
    Add to My Documents
    Premium and Atrium using EcoStruxure™ Control Expert - Discrete I/O modules, User Manual (Version 10)
    Premium and Atrium using EcoStruxure™ Control Expert, Processors, Racks and Power Supply Modules (Version 10)
    Certificate
    Date
    Size
    Add to My Documents
    CSA_225844_1041715_PREMIUM_JUL2011 (Version 1.0)
    UL E486184 - NRAQ-NRAQ7 (Version 1.0)
    Date 12/12/18
    Size 395.6 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    DCC_PREMIUM_JUL2016 (Version 1.0)
    Date 7/20/16
    Size 478.2 KB
    ACMA_RCM_PREMIUM_FEB2015 (Version 1.0)
    Date 2/10/15
    Size 1.9 MB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Marine certificate
    Date
    Size
    Add to My Documents
    MERCHANT_NAVY_PLC_INSTALLATION (Version 1.0)
    Date 1/11/19
    Size 181.4 KB
    DNV-GL Marine Certificate PREMIUM PLCs (Version 1.0)
    BV Marine Certificate PREMIUM PLCs (Version 1.0)
    RINA_ELE104415CS_PREMIUM_APR2015 (Version 1.0)
    Date 4/15/15
    Size 750.3 KB
    RMRS_16.00045.272_PREMIUM_DEC2016 (Version 1.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /