  • Main
    range of product
    Modicon Premium Automation platform
    product or component type
    Discrete output module
    discrete output number
    8
    discrete output type
    Relay protected
    discrete output voltage
    24...240 V AC conforming to EN/IEC 61131-2 20...264 V
    24...48 V DC conforming to EN/IEC 61131-2 19...60 V
    Complementary
    [Ith] conventional free air thermal current
    5 A
    response time
    < 10 ms activation
    < 15 ms deactivation
    contacts type and composition
    2 x 2 C/O + 2 x 2 NO
    output overvoltage protection
    RC circuit and Ge-Mov
    output overload protection
    6.3 A, interchangeable fuse per common fast blow
    short-circuit protection
    6.3 A, interchangeable fuse per common fast blow
    isalotion resistance
    > 10 MOhm 500 V
    power dissipation
    (0.25 W + 0.24 W x No of outputs at state 1)
    electrical durability
    1000000 cycles DC-12 24 W 24 V resistive
    1000000 cycles DC-12 50 W 48 V resistive
    1000000 cycles DC-3 24 W 24 V inductive
    1000000 cycles DC-3 50 W 48 V inductive
    2000000 cycles DC-3 10 W 24 V inductive
    2000000 cycles DC-3 24 W 48 V inductive
    300000 cycles DC-12 100 W 48 V resistive
    300000 cycles DC-12 50 W 24 V resistive
    1000000 cycles AC-12 100 VA 48 V resistive
    2000000 cycles AC-14 50 VA 48 V inductive
    2000000 cycles AC-15 50 VA 48 V inductive
    500000 cycles AC-12 200 VA 48 V resistive
    500000 cycles AC-14 50 VA 24 V inductive
    500000 cycles AC-15 50 VA 24 V inductive
    5000000 cycles AC-14 20 VA 48 V inductive
    5000000 cycles AC-15 20 VA 48 V inductive
    700000 cycles AC-12 100 VA 24 V resistive
    100000 cycles AC-14 440 VA 220...240 V inductive
    100000 cycles AC-15 440 VA 220...240 V inductive
    1000000 cycles AC-12 220 VA 100...120 V resistive
    1000000 cycles AC-12 440 VA 220...240 V resistive
    1000000 cycles AC-14 220 VA 220...240 V inductive
    1000000 cycles AC-15 220 VA 220...240 V inductive
    10000000 cycles AC-14 20 VA 100...120 V inductive
    10000000 cycles AC-14 20 VA 220...240 V inductive
    10000000 cycles AC-15 20 VA 100...120 V inductive
    10000000 cycles AC-15 20 VA 220...240 V inductive
    150000 cycles AC-14 220 VA 100...120 V inductive
    150000 cycles AC-15 220 VA 100...120 V inductive
    1500000 cycles AC-14 110 VA 100...120 V inductive
    1500000 cycles AC-15 110 VA 100...120 V inductive
    3000000 cycles AC-14 110 VA 220...240 V inductive
    3000000 cycles AC-15 110 VA 220...240 V inductive
    500000 cycles AC-12 440 VA 100...120 V resistive
    marking
    CE
    electrical connection
    Screw terminal block
    current consumption
    55 mA 5 V DC
    80 mA 24 V DC rack
    module format
    Standard
    product weight
    0.42 kg
    Environment
    dielectric strength
    2000 V 50/60 Hz 60 s
    standards
    73/23/EEC
    89/336/EEC
    92/31/EEC
    93/68/EEC
    CSA C22.2 No 142
    IEC 61131-2
    UL 508
    CSA C22.2 No 213 Class I Division 2 Group A
    CSA C22.2 No 213 Class I Division 2 Group B
    CSA C22.2 No 213 Class I Division 2 Group C
    CSA C22.2 No 213 Class I Division 2 Group D
    product certifications
    ABS
    BV
    DNV
    GL
    LR
    RINA
    RMRS
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -25...70 °C
    relative humidity
    10...95 % without condensation for operation
    5...95 % without condensation for storage
    operating altitude
    0...2000 m
    protective treatment
    Conformal coating Humiseal 1A33
    TC
    IP degree of protection
    IP20
    pollution degree
    2
    Offer Sustainability
    RoHS (date code: YYWW)
    Compliant  - since  0908  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    User guide
    Date
    Size
    Add to My Documents
    Premium and Atrium using EcoStruxure™ Control Expert, Processors, Racks and Power Supply Modules (Version 10)
    Premium and Atrium using EcoStruxure™ Control Expert - Discrete I/O modules, User Manual (Version 10)
    Certificate
    Date
    Size
    Add to My Documents
    CSA_225844_1041715_PREMIUM_JUL2011 (Version 1.0)
    UL E486184 - NRAQ-NRAQ7 (Version 1.0)
    Date 12/12/18
    Size 395.6 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    DCC_PREMIUM_JUL2016 (Version 1.0)
    Date 7/20/16
    Size 478.2 KB
    ACMA_RCM_PREMIUM_FEB2015 (Version 1.0)
    Date 2/10/15
    Size 1.9 MB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Marine certificate
    Date
    Size
    Add to My Documents
    RINA_ELE104415CS_PREMIUM_APR2015 (Version 1.0)
    Date 4/15/15
    Size 750.3 KB
    RMRS_16.00045.272_PREMIUM_DEC2016 (Version 1.0)
    DNV-GL Marine Certificate PREMIUM PLCs (Version 1.0)
    MERCHANT_NAVY_PLC_INSTALLATION (Version 1.0)
    Date 1/11/19
    Size 181.4 KB
    BV Marine Certificate PREMIUM PLCs (Version 1.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /