    Description
    UPS and four UL 924 listed matching battery cubicles with a minimum of 90 minutes battery operation.
    Model Name
    G5K 100 KVA 480V UPS with SA Batt UL924 BACKUP 90 Min
    Includes
    Installation guide
    Standard Lead Time
    Usually Ships within 2 Weeks
    Product Distribution
    Canada
    General
    Bypass Connection
    4 wire (3Ph + N) or 5 wire (3Ph + N + G)
    Output
    Output Power Capacity
    90.0 KW / 100.0 kVA
    Max Configurable Power (Watts)
    90.0 KW / 100.0 kVA
    Nominal Output Voltage
    480 3PH
    Output Voltage Distortion
    Less than 2%
    Output Frequency (sync to mains)
    60 Hz
    Other Output Voltages
    600V
    Crest Factor
    3 : 1
    Double Conversion Online
    Waveform Type
    Sine wave
    Output Connections
    (1) Hard Wire 4-wire (3PH + G) (Battery Backup)
    Output Voltage Tolerance
    +/- 1% static and +/- 2 % at 100% load step
    Output Voltage THD
    < 1% linear load and < 2.5% nonlinear load
    Overload Operation
    10 minutes @ 125% and 60 seconds @ 150%
    Required Output Current Protection
    144 A
    Bypass
    Internal Bypass (Automatic and Manual)
    Input
    Nominal Input Voltage
    480 3PH
    Input Frequency
    45 - 65 Hz
    Input Connections
    Hard Wire 4-wire (3PH + G)
    Input voltage range for main operations
    408 - 552 (480) V
    Input voltage adjustable range for mains operation
    408 - 552 (480V)V
    Maximum Input Current
    190 A
    Input Breaker Capacity
    250 A
    Maximum Short Circuit Withstand (Icw)
    30.0
    Input Total Harmonic Distortion
    Less than 3% for full load
    Type of Input Protection Required
    3-pole breaker
    Batteries & Runtime
    Battery Type
    No internal battery - uses external battery system
    Communications & Management
    Available SmartSlot™ Interface Quantity
    3
    Control panel
    Multi-function LCD status and control console
    Emergency Power Off (EPO)
    Yes
    Physical
    Maximum Height
    1905.0 mm
    Maximum Width
    5646.0 mm
    Maximum Depth
    813.0 mm
    Net Weight
    8883.64 kg
    Shipping Weight
    8929.09 kg
    Shipping Height
    1930.0 mm
    Shipping Width
    5688.0 mm
    Shipping Depth
    838.0 mm
    Environmental
    Operating Environment
    0 - 40 °C
    Operating Relative Humidity
    5 - 90 %
    Operating Elevation
    0-999.9 meters
    Storage Temperature
    -20 - 45 °C
    Storage Relative Humidity
    0 - 95 %
    Storage Elevation
    0-9000 meters
    Audible noise at 1 meter from surface of unit
    63.000 dB
    Online Thermal Dissipation
    23886.000 BTU/hr
    Protection Class
    IP 20
    Conformance
    Approvals
    UL 1778
    Standard warranty
    1 year on-site repair or replace with factory authorized Start-Up
  • Documents and Downloads

    Language
    • English
    • Latvian
    • Slovenian
    • Danish
    • Lithuanian
    • Greek
    • Croatian
    • Serbian
    • Finnish
    • Norwegian
    • Dutch
    • Estonian
    Catalogue
    Date
    Size
    Add to My Documents
    MGE Galaxy 5000 for Emergency Lighting and Power Equipment (Version 3)
    User guide
    Date
    Size
    Add to My Documents
    Galaxy 5000 40-130 kVA 480 V Installation Manual (NAM) (Version 1)
    Galaxy 5000 40-130 kVA 480 V Receiving & Unpacking (Version 0)
    CAD
    Date
    Size
    Add to My Documents
    SUG5100S90UL - G5K 100kVA UPS 480V Stand alone Battery Cabinet UL924 Backup 90min (Version 1)
    Specification guide
    Date
    Size
    Add to My Documents
    MGE Galaxy 5000 40-130 kVA 480 V Technical Specifications (Version 0)
    Certificate
    Date
    Size
    Add to My Documents
    UL 924 approval for MGE Galaxy 5000 UPS (Version 2)
    Specification for tender
    Date
    Size
    Add to My Documents
    CSI 2004/1995 MGE Galaxy 5000 40-130 kVA 480 V (Version 2)
    CSI 2004/1995 MGE Galaxy 5000 Parallel Module 40-130 kVA 480 V (Version 0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.