Global (English)

Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric RM4TR31 Image

View all Zelio Control Relays

Zelio Control Relays - RM4TR31

Legacy

Schneider Electric RM4TR31 Image
View all Zelio Control Relays
Zelio Control Relays - RM4TR31
Legacy

three-phase network control relay RM4-T - range 160..220 V

Show more characteristics >
Add to My Products Remove from My Products

RM4TR31 is replaced by:
Product
Qty
RM22TR31
Qty
1
Add to My Products Remove from My Products
  • Reason for Substitution: End of life
  • Substitution date: 05 July 2016
  • Main
    range of product
    Zelio Control
    product or component type
    Industrial measurement and control relays
    relay type
    Control relay
    product specific application
    For 3-phase supply
    relay name
    RM4-T
    relay monitored parameters
    Overvoltage and undervoltage detection
    Phase failure detection
    Phase sequence
    time delay type
    Adjustable 0.1...10 s
    measurement range
    160...300 V
    contacts type and composition
    2 C/O
    poles description
    3P
    Complementary
    maximum switching voltage
    440 V AC
    control threshold undervoltage
    160...220 V
    control threshold overvoltage
    220...300 V
    output contacts
    2 C/O
    setting accuracy of the switching threshold
    +/-3 %
    switching threshold drift
    <= 0.06 % per degree centigrade depending permissible ambient air temperature
    <= 0.5 % within the measuring range
    setting accuracy of time delay
    10 P
    time delay drift
    <= 0.07 % per degree centigrade depending on the rated operational temperature
    <= 0.5 % within the measuring range
    hysteresis
    5 % fixed of de-energisation threshold
    run-up delay at power-up
    < 650 ms
    measuring cycle
    <= 80 ms
    marking
    CE
    overvoltage category
    III conforming to IEC 60664-1
    [Ui] rated insulation voltage
    500 V conforming to IEC
    supply frequency
    50/60 Hz +/- 5 %
    operating position
    Any position without
    connections - terminals
    Screw terminals 2 x 1.5 mm², flexible cable with cable end
    Screw terminals 2 x 2.5 mm², flexible cable without cable end
    tightening torque
    0.6...1.1 N.m
    mechanical durability
    <= 30000000 cycles
    [Ith] conventional free air thermal current
    8 A
    [Ie] rated operational current
    2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/1991
    2 A at 70 °C 24 V DC-13 conforming to VDE 0660
    3 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/1991
    3 A at 70 °C 115 V AC-15 conforming to VDE 0660
    3 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/1991
    3 A at 70 °C 24 V AC-15 conforming to VDE 0660
    3 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/1991
    3 A at 70 °C 250 V AC-15 conforming to VDE 0660
    0.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/1991
    0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660
    0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991
    0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
    switching capacity in mA
    10 mA at 12 V
    switching voltage
    250 V AC
    contacts material
    90/10 silver nickel contacts
    number of cables
    2
    height
    78 mm
    width
    22.5 mm
    depth
    80 mm
    terminals description ISO n°1
    (15-16-18)OC
    (25-26-28)OC
    (L1-L2-L3)CO
    output relay state
    Tripped, fault present
    9 mm pitches
    2.5
    product weight
    0.11 kg
    Environment
    electromagnetic compatibility
    Electrostatic discharge - test level 6 kV, level 3 - contact discharge conforming to IEC 61000-4-2
    Electrostatic discharge - test level 8 kV, level 3 - air discharge conforming to IEC 61000-4-2
    Resistance to electrostatic discharge - test level 6 kV - contact conforming to IEC 61000-4-2 level 3
    Resistance to electrostatic discharge - test level 8 kV - air conforming to IEC 61000-4-2 level 3
    standards
    EN/IEC 60255-6
    product certifications
    CSA
    GL
    UL
    directives
    89/336/EEC - electromagnetic compatibility
    73/23/EEC - low voltage directive
    ambient air temperature for storage
    -40...85 °C
    ambient air temperature for operation
    -20...65 °C
    relative humidity
    15...85 % 3K3 conforming to IEC 60721-3-3
    vibration resistance
    0.35 ms (f = 10...55 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn for 11 ms conforming to IEC 60068-2-27
    IP degree of protection
    IP20 (terminals) conforming to IEC 60529
    IP50 (casing) conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    dielectric test voltage
    2.5 kV
    non-dissipating shock wave
    4.8 kV
    resistance to electrostatic discharge
    6 kV contact conforming to IEC 61000-4-2 level 3
    8 kV air conforming to IEC 61000-4-2 level 3
    resistance to electromagnetic fields
    10 V/m conforming to IEC 61000-4-3 level 3
    resistance to fast transients
    2 kV conforming to IEC 61000-4-4 level 3
    disturbance radiated/conducted
    CISPR 11 group 1 - class A
    CISPR 22 - class A
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalogue Page
    Date
    Size
    Add to My Documents
    Date 12/14/17
    Size 129.9 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    3-phase Supply Control Relays
    Dimensions



  • Mounting and Clearance

    3-phase Supply Control Relays
    Rail mounting


    Screw fixing



  • Connections and Schema

    3-Phase Supply Control Relays
    Wiring Diagram


    L1, L2, L3
    Supply to be monitored
    15-18, 15-16
    1st C/O contact of the output relay
    25-28, 25-26
    2nd C/O contact of the output relay


    Application Scheme
    Example


    (1)
    Fault


  • Performance Curves

    Electrical Durability and Load Limit Curves
    AC Load

    Curve 1: Electrical durability of contacts on resistive load in millions of operating cycles


    X
    Current broken in A
    Y
    Millions of operating cycles

    Curve 2: Reduction factor k for inductive loads (applies to values taken from durability Curve 1)


    X
    Power factor on breaking (cos φ)
    Y
    Reduction factor K

    DC Load

    Load limit curve


    X
    Current in A
    Y
    Voltage in V
    1
    L/R = 20 ms
    2
    L/R with load protection diode
    3
    Resistive load



  • Technical Description

    Function Diagram
    Overvoltage and Undervoltage Detection

    Functions "Fault detection delayed" or "Fault detection extended” (by switch selector)


    Legend

    t Time delay

    U 3-phase supply voltage monitored

    S Overvoltage or undervoltage setting

    15/18, 15/16; 25/28, 25/26 Output relays connections

    Relay status: black color = energized.