Global (English)

Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric RM35LV14MW Image

View all Zelio Control Relays

Zelio Control Relays - RM35LV14MW

Physical

Schneider Electric RM35LV14MW Image
View all Zelio Control Relays
Zelio Control Relays - RM35LV14MW
Physical

liquid level control relay RM35-L - 24..240 V AC/DC - 1 C/O

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Level control relay
    relay name
    RM35L
    relay monitored parameters
    Detection by discrete sensors
    time delay type
    Adjustable 0.1...5 s, +/- 10 %
    switching capacity in VA
    1250 VA
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    5 A AC/DC
    power consumption in VA
    <= 5 VA AC
    utilisation category
    AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    Complementary
    reset time
    1000 ms
    4000 ms
    maximum switching voltage
    250 V AC/DC
    [Us] rated supply voltage
    24...240 V AC/DC 50/60 Hz +/- 10 %
    supply voltage limits
    20.4...264 V AC/DC
    control circuit voltage limits
    - 15 % + 10 % Un
    power consumption in W
    <= 1.5 W DC
    output contacts
    1 C/O
    nominal output current
    5 A
    run-up delay at power-up
    0.5 s
    measurement accuracy
    +/- 10 % of the full scale value
    +/- 20 % for the HS range
    repeat accuracy
    +/- 2 % for time delay
    measurement error
    0.5 %/°C with temperature variation
    cable distance between devices
    100 m
    sensitivity adjustment
    5...100 %
    supply current for sensors
    <= 40 mA
    cable capacitance
    <= 10 nF probe cable
    marking
    CE : 73/23/EEC
    CE : EMC 89/336/EEC
    overvoltage category
    III conforming to IEC 60664-1
    insulation resistance
    > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
    > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
    > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
    > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
    > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
    > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
    [Ui] rated insulation voltage
    250 V conforming to IEC 60664-1
    operating position
    Any position without derating
    connections - terminals
    Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    local signalling
    LED green for power ON
    LED yellow for relay ON
    LED yellow for timer ON
    mounting support
    35 mm symmetrical DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    30000000 cycles
    operating rate
    <= 360 operations/hour under full load
    safety reliability data
    MTTFd = 182.6 years
    B10d = 170000
    width
    35 mm
    Environment
    immunity to microbreaks
    100 ms DC
    90 ms AC
    electromagnetic compatibility
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
    standards
    EN/IEC 60255-6
    product certifications
    CSA
    C-Tick
    GL
    GOST
    UL
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C
    relative humidity
    95 % at 55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
    shock resistance
    15 gn for 11 ms conforming to IEC 60255-21-1
    pollution degree
    3 conforming to IEC 60664-1
    dielectric test voltage
    2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
    2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Date 1/9/18
    Size 8.4 MB
    Date 1/9/18
    Size 8.4 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 6/25/18
    Size 5.8 MB
    Date 8/6/18
    Size 1 MB
    UL Listed RM17, RM22, RM35, RM8487
    Date 8/2/18
    Size 213 B
    End of life manual
    Date
    Size
    Add to My Documents
    Product environmental
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Level Control Relays
    Dimensions and Mounting



  • Connections and Schema

    Level Control Relays
    Wiring Diagram



  • Technical Description

    Function Diagrams
    Control of Two Levels

    Fill/Empty function


    Legend

    Un Nominal supply voltage

    (1) Min. level

    (2) Max. level

    11-12/11-14, 21-22/21-24 Output relay connections

    Relay status: black color = energized.

    Control of One Level

    Empty function T on


    Empty function T off


    Fill function T on


    Fill function T off


    Legend

    Tt Time delay after crossing of threshold

    Un Supply voltage

    (1) Level threshold

    11-12/11-14, 21-22/21-24 Output relay connections

    Relay status: black color = energized.