Global (English)

Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric RM35JA32MR Image

View all Zelio Control Relays

Zelio Control Relays - RM35JA32MR

Electrical

Schneider Electric RM35JA32MR Image
View all Zelio Control Relays
Zelio Control Relays - RM35JA32MR
Electrical

Current control relay 0.15A…15A, 2 C/O

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Current control relay
    relay name
    RM35JA
    relay monitored parameters
    Overcurrent or undercurrent detection
    Overcurrent or undercurrent in window mode
    time delay type
    Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
    switching capacity in VA
    2000 VA
    measurement range
    150 mA...15 A current AC/DC 50/60 Hz
    0.15...1.5 A E1-M terminals
    0.5...5 A E2-M terminals
    1.5...15 A E3-M terminals
    Complementary
    reset time
    <= 1500 ms at maximum voltage
    maximum switching voltage
    250 V AC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    8 A AC
    [Us] rated supply voltage
    24...240 V AC/DC, 50/60 Hz (+/- 10 %)
    supply voltage limits
    20.4...264 V AC/DC
    control circuit voltage limits
    - 15 % + 10 % Un
    power consumption in VA
    3.5 VA AC
    power consumption in W
    1.5 W DC
    resistance across terminals
    0.005 Ohm at E3-M terminals
    0.015 Ohm at E2-M terminals
    0.05 Ohm at E1-M terminals
    output contacts
    2 C/O
    nominal output current
    8 A
    internal input resistance
    0.05 Ohm
    0.015 Ohm
    0.005 Ohm
    setting accuracy of the switching threshold
    +/- 10 % of the full scale
    switching threshold drift
    <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    setting accuracy of time delay
    10 P
    time delay drift
    <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    hysteresis
    5...50 % adjustable of threshold setting for overcurrent or undercurrent detection
    3 % fixed of full scale for window mode
    run-up delay at power-up
    0.3 s
    measuring cycle
    100 ms measurement cycle as true rms value
    repeat accuracy
    +/- 0.5 % input and measurement circuit
    +/- 2 % time delay
    measurement error
    < 1 % over the whole range with voltage variation
    0.05 %/°C with temperature variation
    response time
    <= 500 ms on crossing the threshold
    threshold setting
    10...100 %
    overvoltage category
    III conforming to UL 508
    III conforming to IEC 60664-1
    insulation resistance
    > 100 MOhm at 500 V DC conforming to IEC 60255-27
    insulation
    Between supply and measurement
    mounting position
    Any position
    connections - terminals
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    Screw terminals 1 x 0.5...1 x 3.3 mm² - AWG 20...AWG 12, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 14, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    status LED
    LED yellow for relay ON
    LED green for power ON
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    10000000 cycles
    utilisation category
    AC-1 conforming to IEC 60947-4-1
    DC-1 conforming to IEC 60947-4-1
    AC-15 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    safety reliability data
    MTTFd = 296.8 years
    B10d = 270000
    contacts material
    Cadmium free
    width
    35 mm
    product weight
    0.12 kg
    Environment
    immunity to microbreaks
    50 ms
    electromagnetic compatibility
    Conducted and radiated emissions class B conforming to CISPR 22
    Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
    Electrostatic discharge 6 kV level 3 contact discharge conforming to IEC 61000-4-2
    Electrostatic discharge 8 kV level 3 air discharge conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test 10 V/m level 3 conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test 4 kV level 4 direct conforming to IEC 61000-4-4
    Electrical fast transient/burst immunity test 2 kV level 4 capacitive coupling conforming to IEC 61000-4-4
    Surge immunity test 4 kV level 4 common mode conforming to IEC 61000-4-5
    Surge immunity test 2 kV level 4 differential mode conforming to IEC 61000-4-5
    Conducted and radiated emissions class B group 1 conforming to CISPR 11
    Emission standard for residential, commercial and light-industrial environments except radiated emission conforming to EN/IEC 61000-6-3
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Immunity for industrial environments conforming to EN/IEC 61000-6-2
    standards
    EN/IEC 60255-1
    product certifications
    CCC
    CE
    CSA
    GL
    UL
    RCM
    EAC
    China RoHS
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C at 60 Hz
    -20...60 °C at 50 Hz AC/DC
    environmental characteristic
    3K3 level C
    relative humidity
    93...97 % at 25...55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.075 mm (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    1 gn (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    0.035 mm (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    0.5 gn (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    shock resistance
    15 gn for 11 ms (not in operation) conforming to IEC 60068-2-27
    5 gn for 11 ms (in operation) conforming to IEC 60068-2-27
    IP degree of protection
    IP20 on terminals conforming to IEC 60529
    IP50 on front panel conforming to IEC 60529
    IP30 on housing conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    3 conforming to UL 508
    dielectric test voltage
    2.5 kV for 1 min AC 50 Hz conforming to IEC 60255-27
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Danish
    • Russian
    • Czech
    • French
    • Polish
    • Italian
    • Finnish
    • Chinese
    • German
    • Swedish
    • Norwegian
    • Dutch
    Catalogue
    Date
    Size
    Add to My Documents
    Date 1/9/18
    Size 8.4 MB
    Date 1/9/18
    Size 8.4 MB
    Brochure
    Date
    Size
    Add to My Documents
    Date 9/16/17
    Size 5.8 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 8/6/18
    Size 1 MB
    UL Listed RM17, RM22, RM35, RM8487
    Date 8/2/18
    Size 213 B
    Date 6/25/18
    Size 882.9 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Date 9/18/18
    Size 3.9 MB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 11/1/18
    Size 0
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Mounting and Clearance
    Rail Mounting



  • Connections and Schema

    Current Measurement Relay

    Wiring Diagram


    A1,A2 : Supply voltage

    E1,E2,E3,M : Currents to be measured

    11-14,12 : 1st C/O contact of output relay

    21-24,22 : 2nd C/O contact of output relay


  • Technical Description

    Function Diagrams
    Undercurrent Detection

    Without memory ("No Memory" mode)


    With memory ("Memory" mode)


    Overcurrent Detection

    Without memory ("No Memory" mode)


    With memory ("Memory" mode)


    Legend

    Ti Starting inhibition time delay

    Tt Time delay after crossing of threshold

    Un Supply voltage

    I Monitored current

    H Hysteresis

    I> Overcurrent threshold

    I< Undercurrent threshold

    11-12/11-14, 21-22/21-24 Output relay connections

    Relay status: black color = energized.

    NOTE: In "Memory" mode, the relay opens when crossing of the threshold is detected and then stays in that position. The power supply voltage must be switched off to reset the product.