  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Pump control relays
    product specific application
    For 3-phase and single-phase pump
    relay name
    RM35BA
    relay monitored parameters
    Phase failure on 3-phase supply
    Phase sequence on 3-phase supply
    Overcurrent and undercurrent control
    time delay type
    Ti on energisation adjustable 1...60 s, +/- 10 %
    Reset on terminal Y2 fixed 0.3 s
    Tt on crossing the threshold adjustable 0.1...10 s, +/- 10 %
    switching capacity in VA
    1250 VA
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    5 A AC/DC
    power consumption in VA
    <= 5 VA AC
    measurement range
    1...10 A AC
    utilisation category
    AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    Complementary
    reset time
    2000 ms
    maximum switching voltage
    250 V AC/DC
    [Un] rated nominal voltage
    208...480 V AC 3 phases
    230 V AC 1 phase
    [Un] rated nominal voltage
    208...480 V AC 3 phases
    230 V AC single phase
    supply voltage limits
    183...528 V AC
    operating voltage tolerance
    - 15 % + 10 % Un
    resistance across terminals
    0.01 Ohm E1-L2 terminals
    width
    35 mm
    output contacts
    1 C/O
    nominal output current
    5 A
    measuring cycle
    <= 140 ms as true rms value
    delay at power up
    0.5 s
    hysteresis
    5 % of threshold
    measurement accuracy
    +/- 10 % of the full scale value
    repeat accuracy
    +/- 1 % for input and measurement circuit
    +/- 1 % for time delay
    measurement error
    1 % by volt over the whole range
    +/- 0.05 %/°C
    response time
    < 300 ms in the event of a fault
    overload input current
    11 A permanent at 25 °C E1-L2 terminals
    50 A non repetitive < 1 s at 25 °C E1-L2 terminals
    marking
    CE : EMC 89/336/EEC
    CE : 73/23/EEC
    overvoltage category
    III conforming to IEC 60664-1
    insulation resistance
    > 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5
    > 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1
    > 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5
    > 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1
    > 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5
    > 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1
    [Ui] rated insulation voltage
    400 V conforming to IEC 60664-1
    supply frequency
    50/60 Hz +/- 10 %
    operating position
    Any position
    connections - terminals
    Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    status LED
    1 LED green for power ON
    1 LED yellow for fault
    1 LED yellow for relay ON
    mounting support
    35 mm symmetrical DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    30000000 cycles
    operating rate
    <= 360 operations/hour under full load
    Environment
    immunity to microbreaks
    500 ms
    electromagnetic compatibility
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
    standards
    EN/IEC 60255-6
    product certifications
    GL
    GOST
    UL
    CSA
    C-Tick
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C
    relative humidity
    95 % at 55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
    1 gn (f = 57.6...150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
    shock resistance
    15 gn for 11 ms conforming to IEC 60255-21-1
    IP degree of protection
    IP20 (terminals) conforming to IEC 60529
    IP30 (casing) conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    dielectric strength
    2 kV AC 50 Hz (shock wave 4 kV)
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0701  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • French
    • Italian
    • German
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue Relais de mesure et de contrôle - Zelio Control (Version 3.0)
    Zelio Control - Monitoring & Control Relays catalog (Version 3.0)
    CAD
    Date
    Size
    Add to My Documents
    CAD file (on TraceParts) for RM35BA10: pump control relay RM35-BA - range 1..10 A (Version 2.0)
    CAD for RM35BA10: pump control relay RM35-BA - range 1..10 A (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    CSA Certificate RM17, RM22, RM35, RM8487 (Version 1.0)
    UL Listed RM17, RM22, RM35, RM8487 (Version 1.0)
    EAC Certificate RM4 RM17 RM22 RM35 (Version 1.0)
    Zelio Control RM35 CCC Certificate 2011010303495614 (Version 1.0)
    Instruction sheet
    Date
    Size
    Add to My Documents
    RM35BA10 Pump control Relay, Instruction Sheet (Version 05)
    End of Life Information
    Date
    Size
    Add to My Documents
    RM35... Measurement and Control Relay, Product End-of-Life Instructions (Version 1.0)
    RM... Control Relay, Product End-of-Life Instructions (Version 2.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 9/21/19
    Size 195.3 KB
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    RM35... Measurement and Control Relay, Product Environmental profile (Version 1.0)
    RM... Control Relay, Product Environmental Profile (Version 2.0)
    RM35... Measurement Relay, Product Environmental profile (Version 1.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 9/21/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    3-Phase and Single-Phase Pump Control Relays
    Dimensions and Mounting



  • Connections and Schema

    3-Phase and Single-Phase Pump Control Relays
    Wiring Diagrams

    3-phase < 10 A


    Single-phase ∼ 230 V < 10 A


    3-phase > 10 A


    Single-phase ∼ 230 V > 10 A



  • Technical Description

    Function Diagrams
    Single Control Mode

    This mode is designed to control a pump via an external signal. The relay output is closed when the signal is present at Y1 (contact closed). Y2 can be used to reset the relay after a current fault.


    Double Control Mode

    This mode is designed to control a pump via two external control signals (Y1 and Y2). The output relay closes when both input signals are present (Y1 and Y2 closed).


    Current Control

    If the control relay is configured for a single-phase supply, it monitors the current consumed by the pump. If the control relay is configured for a 3-phase supply, it monitors the current, phase sequence and phase failure.

    Overcurrent detection


    Undercurrent Detection


    Legend

    Ti Time delay to inhibit fault monitoring on starting of pump

    Tt Time delay in the event of a fault

    Un 3-phase or single-phase power supply

    I Monitored current

    I < Undercurrent threshold

    I > Overcurrent threshold

    I. Def Presence of a current fault

    11-12, 11-14 Output relay connections

    Relay status: black color = energized.


Compare products: /