three-Phase control relay 183…528Vac, 2 C/O

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Control relay
    network number of phases
    3 phases
    relay name
    RM22TG
    relay monitored parameters
    Phase failure detection
    Phase sequence
    time delay type
    Without
    switching capacity in VA
    2000 VA
    measurement range
    183...528 V voltage AC
    Complementary
    reset time
    <= 1500 ms at maximum voltage
    maximum switching voltage
    250 V AC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    8 A AC
    [Us] rated supply voltage
    208...480 V AC
    supply voltage limits
    183...528 V AC
    operating limits
    183...528 V AC
    power consumption in VA
    15 VA at 480 V AC 60 Hz
    voltage detection threshold
    < 100 V AC
    supply voltage frequency
    50...60 Hz +/- 10 %
    output contacts
    2 C/O
    run-up delay at power-up
    <= 650 ms
    response time
    <= 200 ms
    overvoltage category
    III conforming to UL 508
    III conforming to IEC 60664-1
    insulation resistance
    > 100 MOhm at 500 V DC conforming to IEC 60255-27
    mounting position
    Any position
    connections - terminals
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    Screw terminals 1 x 0.5...1 x 3.3 mm² - AWG 20...AWG 12, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 14, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    status LED
    LED yellow for relay ON
    LED green for power ON
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    10000000 cycles
    utilisation category
    AC-1 conforming to IEC 60947-4-1
    DC-1 conforming to IEC 60947-4-1
    AC-15 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    safety reliability data
    B10d = 850000
    MTTFd = 924.6 years
    contacts material
    Cadmium free
    width
    22.5 mm
    product weight
    0.09 kg
    Environment
    immunity to microbreaks
    <= 10 ms
    electromagnetic compatibility
    Conducted and radiated emissions class B conforming to CISPR 22
    Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
    Electrostatic discharge 6 kV level 3 contact discharge conforming to IEC 61000-4-2
    Electrostatic discharge 8 kV level 3 air discharge conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test 10 V/m level 3 conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test 4 kV level 4 direct conforming to IEC 61000-4-4
    Electrical fast transient/burst immunity test 2 kV level 4 capacitive coupling conforming to IEC 61000-4-4
    Surge immunity test 4 kV level 4 common mode conforming to IEC 61000-4-5
    Surge immunity test 2 kV level 4 differential mode conforming to IEC 61000-4-5
    Conducted and radiated emissions class B group 1 conforming to CISPR 11
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to EN/IEC 61000-6-2
    standards
    EN/IEC 60255-1
    product certifications
    CSA
    CE
    UL
    China RoHS
    RCM
    EAC
    GL
    CCC
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C at 60 Hz
    -20...60 °C at 50 Hz AC/DC
    relative humidity
    93...97 % at 25...55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.075 mm (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    1 gn (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    0.035 mm (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    0.5 gn (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    shock resistance
    15 gn for 11 ms (not in operation) conforming to IEC 60068-2-27
    5 gn for 11 ms (in operation) conforming to IEC 60068-2-27
    IP degree of protection
    IP20 on terminals conforming to IEC 60529
    IP40 on housing conforming to IEC 60529
    IP50 on front panel conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    3 conforming to UL 508
    dielectric test voltage
    2.5 kV for 1 min AC 50 Hz conforming to IEC 60255-27
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0701  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Product end of life instructions
  • Documents and Downloads

    Language
    • English
    • Spanish
    • French
    • Italian
    • Finnish
    • German
    • Chinese
    Catalogue
    Date
    Size
    Add to My Documents
    Zelio Control - Monitoring & Control Relays catalog (Version 3.0)
    Catalogue Relais de mesure et de contrôle - Zelio Control (Version 3.0)
    CAD
    Date
    Size
    Add to My Documents
    CAD for RM22TG20: three-Phase control relay 183…528Vac, 2 C/O (Version 1.0)
    Brochure
    Date
    Size
    Add to My Documents
    Teollisuuden Tähtituotteet 2 (Version 1.0)
    Date 5/10/16
    Size 5.8 MB
    Certificate
    Date
    Size
    Add to My Documents
    CSA Certificate RM17, RM22, RM35, RM8487 (Version 1.0)
    CCC Certificate RM22 RM35 (Version 1.0)
    Date 5/23/19
    Size 1.7 MB
    UL Listed RM17, RM22, RM35, RM8487 (Version 1.0)
    EAC Certificate RM4 RM17 RM22 RM35 (Version 1.0)
    Instruction sheet
    Date
    Size
    Add to My Documents
    RM22... / RM35... Control Relays, Instruction Sheet (Version 04)
    End of Life Information
    Date
    Size
    Add to My Documents
    RM... Control Relay, Product End-of-Life Instructions (Version 2.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 8/26/19
    Size 195.3 KB
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    RM... Control Relay, Product Environmental Profile (Version 2.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 8/26/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Mounting and Clearance
    Rail Mounting



  • Connections and Schema

    3-Phase Control Relay

    Wiring Diagram


    L1,L2,L3 : Supply to be monitored

    11-14,12 : 1st C/O contact of output relay

    21-24,22 : 2nd C/O contact of output relay


  • Technical Description

    Function Diagram
    Phase Sequence Control and Total Loss of Phase Detection


    Legend

    Tr Response time on appearance of a fault

    L1, L2, L3 Phases of the supply voltage monitored

    R - R1/R2 Output relay(s),

    Relay status: black color = energized.


Compare products: /