Global (English)
Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all Sepam series 10
Schneider Electric REL59811 Image

REL59811

Schneider Electric REL59811 Image
REL59811

substat., transfo.- A41E - Sepam series 10

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Sepam series 10
    device short name
    A41E
    relay application
    Transformer
    Substation
    protection type
    Phase overcurrent 50/51
    Thermal overload protection 49RMS
    Earth fault/standard earth fault 50N/51N
    Cold load pick-up Io CPLU 50N/51N
    Cold load pick-up CPLU 50/51
    control and monitoring type
    Logic discrimination 68
    Annunciation 30
    Latching/acknowledgement 86
    metering type
    Earth-fault current
    Peak demand currents
    Phase currents
    network and machine diagnosis type
    Tripping context
    switchgear diagnosis type
    Trip circuit supervision
    communication port protocol
    Modbus
    IEC 60870-5-103
    communication of data
    Reading of measurements
    Reading of status conditions
    Reading of time-stamped measurements and events
    Transmission of remote controls
    Time setting and synchronisation
    physical interface
    RS485
    input output max capacity
    4 inputs + 7 outputs
    communication compatibility
    Modbus RTU
    IEC 60870-5-103
    local signalling
    LEDs fault indication front face
    LEDs Sepam operating status front face
    logic input number
    4 240 V + 20 % AC 47...63 Hz 58 V 3 mA
    4 250 V + 20 % DC 82 V 3 mA
    number of outputs
    3 indication relay
    4 control relay
    output type
    Control relay 100...240 V AC 47...63 Hz 5 A 5 kA cos φ > 0.3 30 A for 200 ms 2000 cycles
    Indication relay 100...240 V AC 47...63 Hz 2 A 1 kA cos φ > 0.3
    Control relay 127 V DC 5 A 0.7 kA resistive 30 A for 200 ms 2000 cycles
    Control relay 220 V DC 5 A 0.1 kA L/R < 40 ms 30 A for 200 ms 2000 cycles
    Control relay 220 V DC 5 A 0.3 kA resistive 30 A for 200 ms 2000 cycles
    Control relay 24 V DC 5 A 4 kA resistive 30 A for 200 ms 2000 cycles
    Control relay 24 V DC 5 A 5 kA L/R < 40 ms 30 A for 200 ms 2000 cycles
    Control relay 48 V DC 5 A 1 kA L/R < 40 ms 30 A for 200 ms 2000 cycles
    Control relay 48 V DC 5 A 4 kA resistive 30 A for 200 ms 2000 cycles
    Indication relay 127 V DC 2 A 0.5 kA L/R < 20 ms
    Indication relay 220 V DC 2 A 0.15 kA L/R < 20 ms
    Indication relay 24 V DC 2 A 2 kA L/R < 20 ms
    Indication relay 48 V DC 2 A 1 kA L/R < 20 ms
    [Us] rated supply voltage
    100...240 V AC +/- 20 %
    110...250 V DC +/- 20 %
    supply inrush current
    < 20 A 0.1 ms
    power consumption in VA
    8 VA maximum
    3 VA typical
    mounting mode
    Fixed
    mounting support
    Plate
    Complementary
    height
    139 mm
    width
    179 mm
    depth
    123 mm
    product weight
    1.46 kg
    Environment
    standards
    UL 508
    EN 50263
    CSA C22.2
    product certifications
    C22.2 file N° 210625
    CE
    UL 508 file N° 212533
    fire resistance
    650 °C IEC 60695-2-11
    IP degree of protection
    IP40 IEC 60529 rear panel
    IP54 IEC 60529 front panel
    NEMA degree of protection
    Type 12 Nema type 250
    IK degree of protection
    IK07 IEC 62262
    power frequency dielectric withstand
    2 kV IEC 60255-27 60 s
    [Uimp] rated impulse withstand voltage
    5 kV IEC 60255-5 1.2/50 µs
    3 kV IEC 60255-27 1.2/50 µs
    immunity to microbreaks
    100 ms CEI 60255-11
    electromagnetic compatibility
    Conducted emission tests A CISPR22
    Conducted emission tests A EN 55022
    Conducted RF disturbances immunity tests-conducted disturbances 10 V, 0.15...80 MHz IEC 60255-22-6
    Conducted RF disturbances immunity tests-conducted disturbances 3 10 V, 0.15...80 MHz IEC 61000-4-6
    Damped oscillatory wave immunity tests-conducted disturbances 2.5 kV CM and DM ANSI C37.90.1
    Damped oscillatory wave immunity tests-conducted disturbances 2.5 kV DM, 1 kV DM, 100 kHz and 1 MHz IEC 60255-22-1
    Damped oscillatory wave immunity tests-conducted disturbances 3 2.5 kV DM, 1 kV DM, 100 kHz and 1 MHz IEC 61000-4-18
    Electrostatic discharge immunity tests-radiated disturbances 8 kV air, 6 kV contact ANSI C37.90.3
    Electrostatic discharge immunity tests-radiated disturbances 8 kV air, 6 kV contact IEC 60255-22-2
    Electrostatic discharge immunity tests-radiated disturbances 3 8 kV air, 6 kV contact IEC 61000-4-2
    Fast transient bursts immunity tests-conducted disturbances 4 kV CM and DM, 5 kHz ANSI C37.90.1
    Fast transient bursts immunity tests-conducted disturbances 4 kV CM, 5kHz IEC 60255-22-4
    Fast transient bursts immunity tests-conducted disturbances 4 4 kV CM, 5kHz IEC 61000-4-4
    Magnetic field at power frequency immunity tests-radiated disturbances 4 30 A/m (continuous) 100 A/m (for 1...3 s) IEC 61000-4-8
    Overall tests A IEC 60255-26
    Power frequency for status inputs immunity tests-conducted disturbances 300 V CM, 150 V DM IEC 60255-22-7
    Power frequency for status inputs immunity tests-conducted disturbances 4 300 V CM, 150 V DM IEC 61000-4-16
    Radiated emission tests A CISPR22
    Radiated emission tests A EN 55022
    Radiated RF fields immunity tests-radiated disturbances 10 V/m, 80...1000 MHz, 1.4...2.7 GHz IEC 60255-22-3
    Radiated RF fields immunity tests-radiated disturbances 20 V/m, 80...1000 MHz ANSI C37.90.2 (2004)
    Radiated RF fields immunity tests-radiated disturbances 3 10 V/m, 80 MHz...2000 MHz IEC 61000-4-3
    Surges immunity tests-conducted disturbances 1.2/50 µs, 10/700 µs, 2 kV CM, 1 kV DM IEC 60255-22-5
    Surges immunity tests-conducted disturbances 3 1.2/50 µs, 10/700 µs, 2 kV CM, 1 kV DM IEC 61000-4-5
    mechanical robustness
    Fire resistance enclosure protection 650 °C IEC 60695-2-11
    Bumps de-energized 2 20 Gn for 16 ms IEC 60255-21-2
    Earthquakes in operation 2 2 Gn horizontal, 1 Gn vertical IEC 60255-21-3
    Front panel enclosure protection IP54 IEC 60529
    Front panel enclosure protection type 12 Nema type 250
    Rear panel enclosure protection IP40 IEC 60529
    Shocks de-energized 2 30 Gn for 11 ms IEC 60255-21-2
    Shocks enclosure protection IK7 2 joules IEC 62262
    Shocks in operation 2 10 Gn for 11 ms IEC 60255-21-2
    Vibrations de-energized 2 2 Gn, 10...150 Hz, 20 cycle IEC 60255-21-1
    Vibrations in operation 2 1 Gn, 10...150 Hz, 1 cycle IEC 60255-21-1
    climatic withstand
    Exposure to cold storage in original packaging - 40 °C (104 °F), 96 h IEC 60068-2-1
    Corrosive atmosphere/2 gas test in operation Ke 21 days, 75 % RH, 25 °C (77 °F), 0.5 ppm H2S, 1 ppm SO2 IEC 60068-2-60
    Exposure to cold in operation Ad - 40 °C (104 °F), 96 h IEC 60068-2-1
    Exposure to damp heat in operation Cab 93 % RH, 40 °C, 56 days IEC 60068-2-78
    Exposure to damp heat storage in original packaging Cab 93 % RH, 40 °C, 56 days IEC 60068-2-78
    Exposure to dry heat in operation Bd 70 °C (158 °F), 96 h IEC 60068-2-2
    Exposure to dry heat storage in original packaging Bd 70 °C (158 °F), 96 h IEC 60068-2-2
    Salt mist in operation Kb/2 6 cycles IEC 60068-2-52
    Temperature variation storage in original packaging Nb 5 °C/min at - 40...70 °C (- 40...158 °F) IEC 60068-2-14
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0810  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    • French
    • Italian
    • German
    User guide
    Date
    Size
    Add to My Documents
    Sepam série 10 - Manuel de référence (FR) (Version 2.0)
    CAD
    Date
    Size
    Add to My Documents
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 80.7 KB
    Date 11/14/07
    Size 12.1 KB
    Date 11/14/07
    Size 464 KB
    Date 11/14/07
    Size 11.5 KB
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 53.1 KB
    Date 11/14/07
    Size 4.9 KB
    Date 11/14/07
    Size 146.8 KB
    Date 11/14/07
    Size 11.5 KB
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 43.1 KB
    Date 11/14/07
    Size 6.7 KB
    Date 11/14/07
    Size 143.9 KB
    Date 11/14/07
    Size 4.6 KB
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 51.1 KB
    Date 11/14/07
    Size 4.8 KB
    Date 11/14/07
    Size 139.2 KB
    Date 11/14/07
    Size 8.9 KB
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 33.7 KB
    Date 11/14/07
    Size 4.2 KB
    Date 11/14/07
    Size 34.3 KB
    Date 11/14/07
    Size 4.7 KB
    Sepam serie 10 N (Version 1.0)
    Date 11/14/07
    Size 43.7 KB
    Date 11/14/07
    Size 5.8 KB
    Date 11/14/07
    Size 150.4 KB
    Date 11/14/07
    Size 6.6 KB
    Sepam serie 10 A (Version 1.0)
    Date 11/14/07
    Size 79.3 KB
    Date 11/14/07
    Size 10.7 KB
    Date 11/14/07
    Size 179.6 KB
    Date 11/14/07
    Size 37.9 KB
    Sepam serie 10 A (Version 1.0)
    Date 12/12/07
    Size 77.5 KB
    Date 12/12/07
    Size 9.4 KB
    Date 12/12/07
    Size 178 KB
    Date 12/12/07
    Size 36.4 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Sepam series 10 A41 - Instruction sheet (EN, FR, IT, DE) (Version 02)
    Catalogue page
    Date
    Size
    Add to My Documents
    Sepam série 10 : catalogue (Version 2.0)
    Date 10/29/08
    Size 1.8 MB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /