Global (English)
Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

RE11RAMU is replaced by:
Product
Qty
RE17RAMU
Qty
1
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4
  • Reason for Substitution: End of life
  • Substitution date: 01 December 2013
1
  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    component name
    RE11R
    time delay type
    A
    At
    time delay range
    1...10 min
    6...60 s
    10...100 h
    6...60 min
    1...10 s
    0.1...1 s
    1...10 h
    [Us] rated supply voltage
    24 V DC
    24...240 V AC 50/60 Hz
    nominal output current
    8 A
    Complementary
    contacts material
    AgNi (cadmium free)
    width pitch dimension
    17.5 mm
    control type
    Selector switch on front panel
    voltage range
    0.85...1.1 Us
    connections - terminals
    Screw terminals, clamping capacity: 2 x 1.5 mm² without cable end
    Screw terminals, clamping capacity: 2 x 2.5 mm² + 1 x 4 mm² with cable end
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    minimum pulse duration
    100 ms with load in parallel
    30 ms
    maximum reset time
    100 ms on de-energisation
    on-load factor
    100 %
    maximum power consumption
    32 VA 240 V
    maximum power consumption
    0.6 W 24 V
    1.5 W 240 V
    minimum switching current
    10 mA
    maximum switching current
    8 A
    maximum switching voltage
    250 V
    breaking capacity
    2000 VA
    breaking capacity
    80 W
    electrical durability
    100000 cycles 8 A at 250 V resistive
    mechanical durability
    5000000 cycles
    [Uimp] rated impulse withstand voltage
    5 kV for 1.2...50 µs conforming to IEC 60664-1
    5 kV for 1.2...50 µs conforming to IEC 61812-1
    marking
    CE
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    surge withstand
    1 kV (differential mode) conforming to IEC 61000-4-5 level 3
    2 kV (common mode) conforming to IEC 61000-4-5 level 3
    mounting support
    35 mm symmetrical mounting rail conforming to EN 50022
    local signalling
    LED indicator green flashing: timing in progress
    LED indicator green on steady: relay energised, no timing in progress
    LED indicator green pulsing: relay energised, no timing in progress
    product weight
    0.06 kg
    Environment
    immunity to microbreaks
    > 10 ms
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
    standards
    73/23/EEC
    IEC 61812-1
    IEC 60669-2-3
    93/68/EEC
    89/336/EEC
    EN 50081-1/2
    EN 50082-1/2
    product certifications
    CSA
    GL
    cULus
    ambient air temperature for storage
    -30...60 °C
    ambient air temperature for operation
    -20...60 °C
    IP degree of protection
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    vibration resistance
    0.35 mm (f = 10...55 Hz) conforming to IEC 60068-2-6
    relative humidity
    93 % without condensation conforming to IEC 60068-2-3
    resistance to electrostatic discharge
    6 kV (in contact) conforming to IEC 61000-4-2 level 3
    8 kV (in air) conforming to IEC 61000-4-2 level 3
    resistance to electromagnetic fields
    10 V/m, 80 MHz to 1 GHz conforming to ENV 50140/204 level 3
    10 V/m, 80 MHz to 1 GHz conforming to IEC 61000-4-3 level 3
    resistance to fast transients
    1 kV, capacitive connecting clip conforming to IEC 61000-4-4 level 3
    2 kV, direct conforming to IEC 61000-4-4 level 3
    immunity to radioelectric fields
    10 V (0.15...80 MHz) conforming to ENV 50141 (IEC 61000-4-6)
    immunity to voltage dips
    30 % / 10 ms conforming to IEC 61000-4-11
    60 % / 100 ms conforming to IEC 61000-4-11
    95 % / 5 s conforming to IEC 61000-4-11
    disturbance radiated/conducted
    Class B conforming to EN 55022 (EN 55011 group 1)
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    CAD file (on TraceParts) for RE11RAMU: on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC (Version 2.0)
    CAD for RE11RAMU: on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC (Version 1.0)
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    RE11... Timer Relay, Product Environmental Profile (Version 1.0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram



  • Technical Description

    Function A : Power on Delay Relay
    Description

    The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function At : Power on Delay Relay (Summation) with Control Signal
    Description

    After power-up, the first opening of control contact C starts the timing. Timing can be interrupted each time control contact closes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output relay closes.

    Function: 1 Output


    T = t1 + t2 +...


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply