Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric R9E50205 Image

Range: Resi9 DB60

DB60 distrib Export

R9E50205

Schneider Electric R9E50205 Image
Range: Resi9 DB60

DB60 distrib Export

R9E50205

Earth leakage circuit breaker for service connection - DB60 - 1P+N - 5A - 500mA

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    Range of product
    Resi9
    product name
    DB60
    product or component type
    Residual current breaker with overcurrent protection (RCBO)
    device location in system
    Main incomer
    Pole
    1P + N
    Maximum current rated
    5 A
    Settings
    5 A corresponding to a power of 1 kVA
    earth-leakage sensitivity
    500 mA
    earth-leakage protection time delay
    Instantaneous
    earth-leakage protection class
    Type AC
    neutral position
    Left
    standards
    NF C 61-450
    electrical insulation class
    Class II
    network type
    AC
    trip unit technology
    Thermal-magnetic
    Safety function
    Cover opening only in open position of the circuit breaker
    Complementary
    network frequency
    50 Hz
    [Ue] rated operational voltage
    250 V AC 50 Hz conforming to NF C 61-450
    residual current tripping technology
    Voltage independent
    breaking capacity
    0.75 kA
    contact position indicator
    Yes
    control type
    Toggle
    mounting support
    Mounting plate
    height
    209 mm
    width
    71 mm
    depth
    73 mm
    mechanical durability
    15000 cycles
    electrical durability
    15000 cycles
    provision for padlocking
    Yes
    Type of connection
    Fixed terminal with an angle of 30° ;cable cross section : 1.5...16 mm²
    tightening torque
    Setting : 1 N.m
    Power terminals : 3.5 N.m
    earth-leakage protection
    Integrated
    Environment
    IP degree of protection
    IP40 front face
    electromagnetic compatibility
    Electrostatic discharge conforming to IEC 61000-4-2 air discharge 15 kV
    Electrostatic discharge conforming to IEC 61000-4-3 contact discharge 8 kV
    Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-4 80 MHz...6 GHz conforming to criteria A 20 V/m
    Electrical fast transient/burst immunity test conforming to IEC 61000-4-5 conforming to criteria A 4.5 kV
    Surge immunity test conforming to IEC 61000-4-6 common mode conforming to criteria A 5 kV
    Surge immunity test conforming to IEC 61000-4-8 differential mode conforming to criteria A 5 kV
    Conducted RF disturbances conforming to IEC 61000-4-16 0.15...80 MHz conforming to criteria A 20 V
    Magnetic field at power frequency conforming to EN 55022-11 1 minute conforming to criteria A 400 A/m
    Magnetic field at power frequency conforming to EN 55022-11 3 s conforming to criteria A 1000 A/m
    relative humidity
    90 % ( 40 °C )
    ambient air temperature for operation
    -5...40 °C
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    DB60 2P Incomer circuit breaker
    Date 12/11/17
    Size 2.7 MB
    Date 12/11/17
    Size 12.1 MB
    DB60 2P Incomer circuit breaker
    Date 12/11/17
    Size 213.2 KB
    Date 12/11/17
    Size 503.6 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Date 7/21/17
    Size 317.1 KB
    Product environmental
    Date
    Size
    Add to My Documents
    Date 7/21/17
    Size 311.2 KB
  • Technical FAQs

    No results found.