The maximum number of products that can be compared is 4

  • Main
    range
    EasyLogic
    product name
    EasyLogic PM11XXH RS
    device short name
    PM1130H
    product or component type
    Dual source energy meter
    Complementary
    power quality analysis
    total harmonic distortion
    device application
    Energy monitoring
    Main or redundant power monitoring
    type of measurement
    Current
    Voltage
    Frequency
    Power factor
    Phase angle
    RPM
    Peak demand power
    Harmonic distorsion (I THD & U THD)
    Active power
    Active energy
    metering type
    Unbalance current
    Power factor and displacement PF (signed, four quadrant)
    Reactive power Q, Q1, Q2, Q3
    Average current Iavg
    Active, reactive, apparent energy (signed, two quadrant)
    Active power P, P1, P2, P3
    Frequency
    Calculated neutral current
    Voltage U21, U32, U13, V1, V2, V3
    Unbalance voltage
    Rotation speed
    Demand power P, Q, S
    Phase currents
    Apparent power S, S1, S2, S3
    Phase current I1, I2, I3 RMS
    Average voltage Vavg
    counter functions
    ON-load source 1 hour counting
    ON hour counting
    ON-load source 2 hour counting
    Power interruption
    [Us] rated supply voltage
    48...277 V AC 45...65 Hz
    48...277 V DC
    network frequency
    60 Hz
    50 Hz
    [In] rated current
    5 A
    1 A
    type of network
    2P
    2P + N
    3P
    1P + N
    3P + N
    maximum power consumption in VA
    4 VA at 240 V between phase and neutral
    maximum power consumption in W
    2 W at 240 V
    display type
    7 segments LED
    display colour
    Red
    messages display capacity
    3 fields of 4 characters
    display digits
    12 digit(s) - 14.2 mm in height
    communication of data
    Last cleared log
    Reading of measurements
    All counters
    Revolution speed
    Instantaneous and demand values
    tamperproof of settings
    Protected by access code
    sampling rate
    32 samples/cycle
    measurement current
    5…6000 mA
    Signal
    Voltage (impedance 5 MOhm)4 x
    Current 0.005...10 A (impedance 0.3 MOhm)6 x
    measurement voltage
    35…480 V AC 50...60 Hz between phases
    35…277 V AC 50...60 Hz between phase and neutral
    277…999000 V AC 50...60 Hz with external VT
    frequency measurement range
    45…65 Hz
    measurement accuracy
    Current +/- 0.5 %
    Voltage +/- 0.5 %
    Frequency +/- 0.05 %
    Power factor +/- 0.01
    Reactive power +/- 2 %
    Reactive energy +/- 2 %
    Active power +/- 0.5 %
    Apparent power +/- 0.5 %
    Active energy +/- 0.5 %
    Apparent energy +/- 0.5 %
    Harmonic distorsion (I THD & U THD) +/- 5 %
    accuracy class
    Class 2 reactive energy conforming to IEC 62053-23
    Class 0.5 active energy conforming to IEC 62053-22
    number of outputs
    1 relay
    output voltage
    300 V AC 2 A
    Demand intervals
    1 s
    local signalling
    Green LED: activity
    Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
    Red LED: alternate source
    communication port protocol
    Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
    communication port support
    RS485
    data recording
    Energy consumption logs
    material
    Polycarbonate
    flame retardance
    V-0 conforming to UL 94
    mounting mode
    Flush-mounted
    mounting support
    Framework
    provided equipment
    Installation guide
    installation category
    III
    type of installation
    Indoor installation
    measurement category
    Category III 480 V
    electrical insulation class
    Class II
    connections - terminals
    Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s)
    Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
    Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
    Communication: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s)
    Secondary circuit: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s)
    Relay output: screw clamp terminals (rear) 0.33…3.31 mm² cable(s)
    tightening torque
    Current circuit: 0.9…1 N.m Philips No 2 screwdriver
    Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver
    Control circuit: 0.9…1 N.m Philips No 2 screwdriver
    Communication: 0.5…0.6 N.m Philips no 1 screwdriver
    Secondary circuit: 0.5…0.6 N.m Philips no 1 screwdriver
    Relay output: 0.5…0.6 N.m Philips no 1 screwdriver
    wire stripping length
    Current circuit: 3.68 mm
    Voltage circuit: 7 mm
    Control circuit: 7 mm
    Communication: 7 mm
    7 mm
    standards
    IEC 61010-1:ed. 3
    UL 61010-1:ed. 3
    product certifications
    CE conforming to IEC 61010-1
    CULus conforming to UL 61010-1
    CULus conforming to CSA C22.2 No 61010-1
    C-Tick
    width
    96 mm
    depth
    13 mm outside:
    52 mm panel:
    height
    96 mm
    net weight
    300 g
    Environment
    electromagnetic compatibility
    Electrostatic discharge conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
    Surge immunity test conforming to IEC 61000-4-5
    Conducted RF disturbances conforming to IEC 61000-4-6
    Magnetic field at power frequency conforming to IEC 61000-4-8
    Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
    Emission tests conforming to FCC part 15 class A
    Emission tests conforming to FCC part 15 subpart C
    Emission tests conforming to FCC part 15 subpart E
    overvoltage category
    III
    IP degree of protection
    IP51 front: conforming to IEC 60529
    IP30 body: conforming to IEC 60529
    relative humidity
    5…95 % at 50 °C
    pollution degree
    2
    ambient air temperature for operation
    -10…60 °C
    ambient air temperature for storage
    -20…70 °C
    operating altitude
    <= 2000 m
    service life
    7 year(s)
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    REACh free of SVHC
    Yes
    EU RoHS Directive
    Under investigation
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
  • Documents

    Language
    • English
    • Spanish
    • Chinese
    • Turkish
    Catalogue
    Date
    Size
    Add to My Documents
    EasyLogic Catalogue - Print Version (Version 2.1)
    EasyLogic Catalogue - Web Version (Version 2.1)
    User guide
    Date
    Size
    Add to My Documents
    EasyLogic™ PM1130H Conzerv™ EM6438H – User manual - ZH (Version 01)
    EasyLogic™ PM1130H Conzerv™ EM6438H User Manual - TK (Version 01)
    EasyLogic™ PM1130H Conzerv™ EM6438H User Manual - ES (Version 01)
    EasyLogic™ PM1130H Conzerv™ EM6438H User Manual (Version 01)
    Brochure
    Date
    Size
    Add to My Documents
    EasyLogic Panorama - Print Version (Version 2.1)
    Certificate
    Date
    Size
    Add to My Documents
    ECDEM64xxH_PM11xxH_DM6xxxH (Version 1.0)
    Date 1/2/19
    Size 211.4 KB
    SDOC-EM64xx_DM6xxxH_PM11xxH (Version 1.0)
    Date 1/2/19
    Size 262 KB
    UL CoC (Version 1.0)
    Date 1/23/19
    Size 619 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    ECDEM64xxH_PM11xxH_DM6xxxH_UM21xx-V2a.pdf (Version 1.0)
    End of Life Information
    Date
    Size
    Add to My Documents
    EoLI - Easylogic PM1130 (Version 1.0)
    Date 7/5/17
    Size 541.7 KB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
    Technical leaflet
    Date
    Size
    Add to My Documents
    EasyLogic PM1130H Meter - Technical Datasheet - Web (Version 2.1)
    EasyLogic PM1130H Meter - Technical Datasheet - Print (Version 2.1)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /