The maximum number of products that can be compared is 4

  • Main
    range
    Masterpact
    device short name
    Micrologic 3.0 X
    product or component type
    Control unit
    device application
    Equipment protection, monitoring and control
    range compatibility
    Masterpact MTZ1 circuit breaker
    Masterpact MTZ2 circuit breaker
    Masterpact MTZ3 circuit breaker
    commercial reference
    LV839207
    LV839219
    LV839203
    LV839213
    Poles
    4P
    3P
    Protected poles
    4P 3d + OSN
    3P 3d
    4P 4d
    4P 3d
    4P 3d + N/2
    circuit breaker application
    Distribution UL/ANSI standard
    network type
    AC
    trip unit name
    Micrologic 3.0X
    trip unit technology
    Electronic
    trip unit protection functions
    LI
    protection type
    Instantaneous short-circuit protection conforming to ANSI 50
    Overload (long time) conforming to ANSI 49
    trip unit rating
    3600 A
    400 A
    4000 A
    1000 A
    1200 A
    800 A
    600 A
    2500 A
    1600 A
    5000 A
    3200 A
    3000 A
    2000 A
    6000 A
    Complementary
    network frequency
    50/60 Hz
    mounting mode
    Fixed
    [Ir] long time pick-up adjustment range
    0.4...1 x In adjustable in step of 1 A
    [tr] long-time delay adjustment range
    12.5…600 s at 1.5 x Ir
    0.5…24 s at 6 x Ir
    0.7…16.6 s at 7.2 x Ir
    long time delay adjustment type
    Adjustable in step of 0.5 s
    [Ii] instantaneous pick-up adjustment range
    1.5...12 x In adjustable in step of 0.5 x In with embedded HMI
    1.5...12 x In adjustable in step of 0.1 x In with Ecoreach software or Masterpact MTZ mobile app
    instantaneous pick-up adjustment type Ii
    Adjustable
    zone selective interlocking ZSI
    Without
    type of measurement
    Power meter
    thermal memory
    Yes
    energy management
    Measurement active, reactive and apparent energy standard)
    Measurement electrical network standard)
    Measurement energy standard)
    metering type
    Average voltage Vavg standard)
    Power factor standard)
    Frequency standard)
    Total current harmonic distortion THD (I): inst, avg, avg min, avg max fundamental voltage standard)
    Total current harmonic distortion THD (I): inst, avg, avg min, avg max RMS voltage standard)
    Total voltage harmonic distortion THD (V): inst, avg, avg min, avg max fundamental voltage standard)
    Total voltage harmonic distortion THD (V): inst, avg, avg min, avg max RMS voltage standard)
    Demand power P, Q, S standard)
    Current Ia, Ib, Ic, In, Ig: maximum standard)
    Active power P, Pa, Pb, Pc standard)
    Reactive power Q, Qa, Qb, Qc standard)
    Apparent power S, Sa, Sb, Sc standard)
    Voltage Vba, Vcb, Vac, Va, Vb, Vc: instantaneous standard)
    Voltage Vba, Vcb, Vac, Va, Vb, Vc: minimum standard)
    Voltage Vba, Vcb, Vac, Va, Vb, Vc: maximum standard)
    Demand current Ia, Ib, Ic, In, Iavg standard)
    network and machine diagnosis type
    System (HMI) health state overview: circuit breaker health state standard)
    Contacts state: circuit breaker health state standard)
    Micrologic service life: circuit breaker health state standard)
    Tripping cause indication: circuit breaker tripping cause standard)
    Identification card: diagnostic data standard)
    Configured alarms synthesis: diagnostic data standard)
    Monitored function: diagnostic data standard)
    Operation: diagnostic data standard)
    Micrologic test: test standard)
    Protection test: test standard)
    Selectivity test: test standard)
    Trip context information: crisis management standard)
    Operation: advanced diagnostic standard)
    Breaker service life: circuit breaker health state standard)
    measurement voltage
    145.6 V AC 50/60 Hz per phase
    828 V AC 50/60 Hz per phase
    frequency measurement range
    40…70 Hz
    measurement accuracy
    Power factor: +/- 1 %
    Active energy Ep IN/OUT/tot: +/- 1 % - 10...10 GWh
    Reactive energy Ep IN/OUT/tot: +/- 2 % - 10...10 GVARh
    Apparent energy Es IN/OUT/tot: +/- 1 % - 10...10 GVAh
    Unbalance current: +/- 0.5 %
    Frequency: +/- 0.005 Hz
    Voltage Vba, Vcb, Vac, Vllavg: +/- 0.5 % 208...690 x 1.2 V
    Voltage Vba, Vcb, Vac, Vlnavg: +/- 0.5 % 120...400 x 1.2 V
    Apparent power S, Sa, Sb, Sc, Sdemand: +/- 1 %
    Active power P, Pa, Pb, Pc, Pdemand: +/- 1 %
    Reactive power Q, Qa, Qb, Qc, Qdemand: +/- 2 %
    Current Ia, Ib, Ic, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A
    Current Ia, Ib, Ic, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A
    Current Ia, Ib, Ic, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A
    accuracy class
    Class 5: total current harmonic distortion THD (I)
    Class 0.5: unbalance voltage
    Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h)
    Class 2: total voltage harmonic distortion THD (V)
    display type
    LCD display - 128 x 96 pixels
    communication port protocol
    Bluetooth 4.0 LE peer to peer 30 kbit/s
    NFC peer to peer 28800 bauds conforming to ISO 15963
    USB peer to peer 115 kbauds
    data recording
    Maintenance logs
    Min/max of instantaneous values
    Data logs
    Time stamping
    Event logs
    Alarm logs
    electromagnetic compatibility
    Electrostatic discharge immunity test conforming to IEC 61000-4-2
    Susceptibility to electromagnetic fields conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
    1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
    Conducted RF disturbances conforming to IEC 61000-4-6
    Conducted and radiated emissions A conforming to CISPR 22
    Environment
    standards
    EN/IEC 60947-2
    EN/IEC 60255-1
    IEC 60092-202
    EN/IEC 60947-1
  • Documents

    Language
    • English
    • Spanish
    • French
    • Chinese
    User guide
    Date
    Size
    Add to My Documents
    Masterpact MTZ Micrologic X - 控制单元 - 用户指南 (Version 04)
    Masterpact MTZ Micrologic X - Unité de contrôle - Guide d'exploitation (Version 04)
    Masterpact MTZ Micrologic X - Unidad de control - Guía del usuario (Version 04)
    Masterpact MTZ Micrologic X Control Unit - User Guide (Version 04)
  • Software and Firmware

    Language
    • English
    Software - Release Notes
    Date
    Size
    Add to My Documents
    Micrologic Firmware History (Version 01)
    Date 3/1/19
    Size 728.9 KB
    Masterpact MTZ Micrologic X Control Unit - Firmware Release Note (Version 06)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /