Global (English)
Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all TeSys D
Schneider Electric LC3D80FE7 Image

LC3D80FE7

Schneider Electric LC3D80FE7 Image
LC3D80FE7

TeSys D - star delta starter - 3 x 3P (3 NO) - 80 A - 115 V AC coil

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range
    TeSys
    product name
    TeSys D
    product or component type
    Star delta starter
    device short name
    LC3D
    contactor application
    Motor control
    utilisation category
    AC-3
    device presentation
    Pre-wired
    poles description
    3 x 3P
    power pole contact composition
    3 x 3 NO
    [Ue] rated operational voltage
    <= 690 V AC 25...400 Hz for power circuit
    [Ie] rated operational current
    80 A (<= 60 °C) AC AC-3 for power circuit at <= 440 V
    motor power kW
    37 kW at 220/230 V AC 50/60 Hz
    75 kW at 380/400 V AC 50/60 Hz
    75 kW at 415 V AC 50/60 Hz
    75 kW at 440 V AC 50/60 Hz
    control circuit type
    AC 50/60 Hz
    [Uc] control circuit voltage
    115 V AC 50/60 Hz
    auxiliary contact composition
    1 NC for KM2 line contactor
    1 NO for KM3 delta contactor
    [Uimp] rated impulse withstand voltage
    8 kV conforming to IEC 60947
    overvoltage category
    III
    [Ui] rated insulation voltage
    600 V certifications CSA power circuit
    600 V certifications UL power circuit
    600 V certifications CSA signalling circuit
    600 V certifications UL signalling circuit
    1000 V conforming to IEC 60947-4-1 power circuit
    1000 V conforming to IEC 60947-1 signalling circuit
    electrical durability
    10 Mcycles 80 A AC-3 <= 440 V
    mounting support
    Plate
    standards
    IEC 60947-5-1
    EN 60947-5-1
    UL 508
    EN 60947-4-1
    IEC 60947-4-1
    CSA C22.2 No 14
    product certifications
    UL
    CCC
    GL
    GOST
    BV
    DNV
    CSA
    RINA
    LROS (Lloyds register of shipping)
    Complementary
    connections - terminals
    Screw clamp terminals for control circuit 1 1...4 mm² flexible without cable end
    Screw clamp terminals for control circuit 2 1...4 mm² flexible without cable end
    Screw clamp terminals for control circuit 2 1...2.5 mm² flexible with cable end
    Screw clamp terminals for control circuit 1 1...4 mm² solid without cable end
    Screw clamp terminals for control circuit 2 1...4 mm² solid without cable end
    Screw clamp terminals for power circuit 1 4...50 mm² flexible without cable end
    Screw clamp terminals for power circuit 2 4...25 mm² flexible without cable end
    Screw clamp terminals for power circuit 1 4...50 mm² flexible with cable end
    Screw clamp terminals for power circuit 2 4...16 mm² flexible with cable end
    Screw clamp terminals for power circuit 1 4...50 mm² solid without cable end
    Screw clamp terminals for power circuit 2 4...25 mm² solid without cable end
    Screw clamp terminals for control circuit 1 1...2.5 mm² flexible with cable end
    tightening torque
    1.7 N.m for control circuit screw clamp terminals flat Ø 6 mm
    1.7 N.m for control circuit screw clamp terminals Philips No 2
    9 N.m for power circuit screw clamp terminals flat Ø 6...8 mm
    mechanical durability
    4 Mcycles
    operating rate
    30 cyc/h at <= 60 °C
    starting time
    30 s
    coil technology
    Without built-in suppressor module
    control circuit voltage limits
    0.3...0.6 Uc at 55 °C drop-out 50/60 Hz
    0.8...1.1 Uc at 55 °C operational 50 Hz
    0.85...1.1 Uc at 55 °C operational 60 Hz
    inrush power in VA
    140 VA at 20 °C 0.75 60 Hz
    160 VA at 20 °C 0.75 50 Hz
    hold-in power consumption in VA
    13 VA at 20 °C 0.3 60 Hz
    15 VA at 20 °C 0.3 50 Hz
    heat dissipation
    4...5 W at 50/60 Hz
    auxiliary contacts type
    Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
    Mirror contact conforming to IEC 60947-4-1 3 x 1 NC
    signalling circuit frequency
    25...400 Hz
    minimum switching current
    For signalling circuit
    minimum switching voltage
    17 V for signalling circuit
    non-overlap time
    1.5 ms on energisation between NC and NO contact
    1.5 ms on de-energisation between NC and NO contact
    width
    311 mm
    height
    143 mm
    depth
    183 mm
    product weight
    5.2 kg
    Environment
    insulation resistance
    > 10 MOhm for signalling circuit
    IP degree of protection
    IP2x front face conforming to IEC 60529
    protective treatment
    TH conforming to IEC 60068-2-30
    pollution degree
    3
    ambient air temperature for storage
    -60...80 °C
    ambient air temperature for operation
    -40...70 °C at Uc
    operating altitude
    3000 m without derating
    fire resistance
    850 °C conforming to IEC 60695-2-1
    flame retardance
    V1 conforming to UL 94
    mechanical robustness
    Vibrations contactor open 2 Gn, 5...300 Hz
    Shocks contactor open 8 Gn for 11 ms
    Vibrations contactor closed 3 Gn, 5...300 Hz
    Shocks contactor closed 10 Gn for 11 ms
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  1801  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue TeSys - 2019 - Chapitre A2 - Démarreurs-moteurs nus pré-cablés (Version 4.0)
    Tesys catalogue 2019 - 2020 Motor control and protection components (Version 9.2)
    TeSys catalogue - 2019 - 2020 - chapter A2 - open, pre-cabled motor starters (Version 6.0)
    Catalogue TeSys 2019 - Composants pour protection et commande de moteurs (Version 7.1)
    End of Life Information
    Date
    Size
    Add to My Documents
    TeSys LC1F185-225 - EoLi (Version 2.0)
    Date 12/1/15
    Size 181.1 KB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    TeSys contactor LC1F (Version 2.0)
    Date 9/8/15
    Size 197.1 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /