    Vigilohm
    device short name
    IM10-H
    product or component type
    Insulation monitoring device
    device application
    Hospital
    earthing system
    IT
    language
    Chinese
    English
    French
    German
    Italian
    Portuguese
    Russian
    Spanish
    Complementary
    network rated voltage
    0...230 V AC 50/60 Hz phase to neutral
    0...100 V DC
    resistance measurement per channel
    No
    type of measurement
    Network insulation resistance : 1 kOhm...10 MOhm
    local signalling
    Green indicator light : satisfactory insulation resistance
    Orange indicator light : below fault threshold
    threshold setting
    Fault : 50...500 kOhm
    response time
    <= 1 s
    auxiliary supply voltage
    125...250 V - DC +/- 15 %
    110...230 V - AC at 50/60 Hz +/- 15 %
    power consumption in VA
    12 VA
    measurement voltage
    25 V
    measurement current
    0...0.2 mA
    internal impedance
    110 kOhm - AC at 50/60 Hz
    test function
    Manual
    output contact
    1 C/O standard or fail-safe
    breaking capacity
    250 V - AC at 6 A
    12...24 V - DC at 6 A
    communication port protocol
    -
    display type
    Digital display
    mounting mode
    Flush-mounted
    Clip-on
    mounting support
    DIN rail
    Panel
    connections - terminals
    Removable screw terminal block 0.2...2.5 mm²
    material
    Thermoplastic
    product weight
    0.25 kg
    height
    110 mm
    width
    96 mm
    depth
    59 mm
    Environment
    dielectric strength
    4000 V - AC
    5500 V - DC
    IP degree of protection
    Front face : IP52
    environmental characteristic
    Exposure to damp heat not in service conforming to IEC 60068-2-30
    Exposure to damp heat in service conforming to IEC 60068-2-56
    Salt mist conforming to IEC 60068-2-52
    pollution degree
    2
    type of installation
    Indoor
    standards
    IEC 61010-1
    IEC 61557-8
    IEC 60364-7-710
    IEC 61326-2-4
    product certifications
    BV
    CE
    DNV
    EAC
    ambient air temperature for operation
    -25...55 °C
    ambient air temperature for storage
    -40...70 °C
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
    Contractual warranty
    Warranty period
    18 months
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.