    Highly efficient, scalable, 3-phase power protection with flexible operating modes and ECOnversion™ for large facilities, data centers, and business critical applications.
    Model Name
    Galaxy VX 1250kVA N+1 Redundant UPS 480V, Start up 5x8
    Includes
    Installation guide , Network Management Card , Start-Up Service
    Standard Lead Time
    Special Order - Call for Quoted Lead Times
    Product Distribution
    Brazil , Canada , Colombia , Costa Rica , Dominican Republic , Ecuador , El Salvador , Guatemala , Honduras , Mexico , Nicaragua , Panama , Puerto Rico , United States , Venezuela
    Output
    Output Power Capacity
    1.25 MW / 1.25 MVA
    Max Configurable Power (Watts)
    1.25 MW / 1.25 MVA
    Nominal Output Voltage
    480 3PH
    Output Frequency (sync to mains)
    60 Hz
    Crest Factor
    3 with THC <5%
    Double Conversion Online
    Waveform Type
    Sine wave
    Output Voltage THD
    < 2% linear load and <3% non-linear load
    Overload Operation
    150% for 1 minute 125% for 10 minutes
    Input
    Nominal Input Voltage
    480 3PH
    Input Frequency
    40 - 70 Hz
    Maximum Input Current
    1820 A
    Maximum Short Circuit Withstand (Icw)
    100.0
    Input Total Harmonic Distortion
    Less than 3% for full load
    Batteries & Runtime
    Battery Type
    No internal battery - uses external battery system
    Nominal Battery Voltage
    480V
    End of Discharge Battery Voltage
    384 Vdc
    Communications & Management
    Available SmartSlot™ Interface Quantity
    2
    Pre-Installed SmartSlot™ Cards
    AP9635
    Control panel
    7" Touch Screen Display
    Audible Alarm
    Audible and visible alarms prioritized by severity
    Physical
    Maximum Height
    1970.0 mm
    Maximum Width
    5600.0 mm
    Maximum Depth
    900.0 mm
    Net Weight
    3990.0 kg
    Shipping Weight
    5129.0 kg
    Shipping Height
    2150.0 mm
    Shipping Width
    6640.0 mm
    Shipping Depth
    1060.0 mm
    Color
    White
    Environmental
    Operating Environment
    0 - 40 °C
    Operating Relative Humidity
    0 - 95 (non-condensing) %
    Operating Elevation
    0-999.9 meters
    Storage Temperature
    -15 - 40 °C
    Storage Relative Humidity
    0 - 95 (non-condensing) %
    Storage Elevation
    0-15000 meters
    Audible noise at 1 meter from surface of unit
    68.000 dB
    Online Thermal Dissipation
    173085.000 BTU/hr
    Protection Class
    IP 20
    Conformance
    Approvals
    CBC 2013 to Sds = 1.84g , CSA C22.2 NO. 107.3 , FCC Part 15 Class A , IBC 2012 , IEC 60721-4-2 Level 2M2 , IEC 62040-3 , OSHPD , UL 1778 5th edition
    Standard warranty
    1 year on-site repair or replace with factory authorized Start-Up
    Sustainable Offer Status
    RoHS
    Compliant
    REACH
    REACH: Contains No SVHCs
    Battery Directive
    Compliant
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Latvian
    • Slovenian
    • Danish
    • French
    • Serbian
    • Finnish
    • Chinese
    • Norwegian
    • Dutch
    • Turkish
    • Russian
    • Greek
    • Lithuanian
    • Croatian
    • Polish
    • Italian
    • German
    • Swedish
    • Estonian
    Catalogue
    Date
    Size
    Add to My Documents
    Galaxy VX 500 to 1500kW 480V Brochure (Version 2)
    User guide
    Date
    Size
    Add to My Documents
    Galaxy VX Operation Manual (Version 6)
    Date 2/7/19
    Size 4.2 MB
    Galaxy VX Operation Manual (Version 6)
    Date 2/7/19
    Size 4.5 MB
    Galaxy VX Operation Manual (Version 6)
    Date 2/7/19
    Size 4.5 MB
    Galaxy VX Receiving and Unpacking (Version 2)
    Galaxy VX ASI de 1 000 kW (extensible), 1 250 kW et 1 500 kW Installation (Version 4)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX Operation Manual (Version 6)
    Galaxy VX 500kW (Expandable), 750kW (Expandable),1000 kW (Expandable), 1250 kW, and 1500 kW Installation Manual (Version 4)
    Galaxy VX Modbus Register Map (Version 0)
    Galaxy VX Operation Manual (Version 6)
    CAD
    Date
    Size
    Add to My Documents
    GVX1500K1250GCBC-SD - Galaxy VX 1250kVA N+1 Redudant UPS 480V System One line (Version 3)
    Specification guide
    Date
    Size
    Add to My Documents
    Galaxy VX 480 V Technical Specifications (Version 5)
    Certificate
    Date
    Size
    Add to My Documents
    CB certificate for Galaxy VX 500KW/KVA modular up to 1500KW/KVA, incl. Power cabinet for modular build GVXP250KD (Version 0)
    Galaxy VX 480 V Certificate of Origin (Version 1)
    GALAXY 500KW/KVA to GALAXY 1500KW/KVA UL1778 5'th edition letter of Authorization (Version 0)
    Galaxy VX OSHPD Pre-approval Letter (Version 1)
    Specification for tender
    Date
    Size
    Add to My Documents
    CSI 2004/1995 Galaxy VX 500kW Expandable to 1500kVA N+1 Internal Redundancy (480V) (Version 6)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.