You can choose another country to view available products or go to our Global website for company information.
Description |
UPS is designed to meet the marine standard requirement.
| |
---|---|---|
Model Name |
MGE Galaxy 5500 20kVA 400-415V Integrated Parallel UPS Marine IP22 RAL 7035, Start-up 5X8
| |
Includes |
Installation guide , User Manual
| |
Standard Lead Time |
Special Order - Call for Quoted Lead Times
| |
Product Distribution |
Albania , Algeria , Andorra , Angola , Anguilla , Antigua And Barbuda , Argentina , Armenia , Aruba , Austria , Azerbaijan , Bahamas , Bahrain , Barbados , Belarus , Belgium , Belize , Benin , Bermuda , Bolivia , Bosnia And Herzegovina , Botswana , Brazil , Bulgaria , Burkina Faso , Burundi , Cameroon , Canada , Cayman Islands , Central African Republic , Chad , Chile , China , Colombia , Congo , CONGO, THE DEMOCRATIC REPUBLIC OF THE , Costa Rica , Cote D'Ivoire , Croatia , Cuba , Cyprus , Czech Republic , Denmark , Djibouti , Dominica , Dominican Republic , Ecuador , Egypt , El Salvador , Equatorial Guinea , Eritrea , Estonia , Ethiopia , Falkland Islands (Malvinas) , Finland , France , Gabon , Gambia , Georgia , Germany , Ghana , Gibraltar , Greece , Grenada , Guadeloupe , Guatemala , Guinea , Guyana , French Guiana , Haiti , Honduras , Hong Kong , Hungary , Iceland , Iran (Islamic Republic Of) , Iraq , Ireland , Israel , Italy , Jamaica , Jordan , Kazakhstan , Kenya , Kuwait , Latvia , Lebanon , Lesotho , Liberia , Liechtenstein , Lithuania , Luxembourg , Macedonia , Madagascar , Malawi , Mali , Malta , Martinique , Mauritania , Mauritius , Mayotte , Mexico , Moldova, Republic Of , Mongolia , Morocco , Mozambique , Namibia , Netherlands , Netherlands Antilles , Nicaragua , Niger , Nigeria , Norway , Oman , Pakistan , Panama , Paraguay , Peru , Poland , Portugal , Puerto Rico , Qatar , Reunion , Romania , Russian Federation , Rwanda , SAINT KITTS AND NEVIS , SAINT LUCIA , SAINT VINCENT AND THE GRENADINES , Saudi Arabia , Senegal , Sierra Leone , Slovakia (Slovak Republic) , Slovenia , Somalia , South Africa , Spain , Sudan , Suriname , Sweden , Switzerland , Taiwan , Tajikistan , TANZANIA, UNITED REPUBLIC OF , Togo , Trinidad And Tobago , Turkey , Turkmenistan , Turks And Caicos Islands , Uganda , Ukraine , United Arab Emirates , United States , Uruguay , Uzbekistan , Venezuela , VIRGIN ISLANDS (UNITED STATES) , Western Sahara , Yemen , Zambia , Zimbabwe
|
Bypass Connection |
4 wire (3Ph + N) or 5 wire (3Ph + N + G)
| |
---|---|---|
Bypass Voltage Tolerance |
+/-10% settable from +/-4/6/8 and 10%
| |
Max Bypass Input Current |
29 A
| |
Bypass Protection Device |
100 A
|
Output Power Capacity |
18.0 KW / 20.0 kVA
| |
---|---|---|
Max Configurable Power (Watts) |
18.0 KW / 20.0 kVA
| |
Nominal Output Voltage |
400 3PH
| |
Output Voltage Note |
Configurable for 400 or 415V 3 Phase nominal output voltage
| |
Output Voltage Distortion |
Less than 2%
| |
Output Frequency (sync to mains) |
50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
| |
Other Output Voltages |
380, 415V
| |
Crest Factor |
3 : 1
| |
Double Conversion Online
| ||
Waveform Type |
Sine wave
| |
Output Voltage Tolerance |
+/- 2% static and 100% load step
| |
Output Voltage THD |
< 1% linear load and < 2.5% nonlinear load
| |
Overload Operation |
10 minutes @ 125% and 60 seconds @ 150%
| |
Required Output Current Protection |
29 A
| |
Neutral Output Current |
43 A
| |
Bypass |
Built-in Maintenance Bypass , Built-in Static Bypass , Optional External Bypass
|
Nominal Input Voltage |
400 3PH
| |
---|---|---|
Input Frequency |
45 - 65 Hz
| |
Input Connections |
Hard Wire 4-wire (3PH + G)
| |
Input voltage range for main operations |
323 - 437 (380V) V , 340 - 460 (400V) V , 353 - 477 (415V) V
| |
Other Input Voltages |
380 , 415
| |
Maximum Input Current |
42 A
| |
Input Breaker Capacity |
125 A
| |
Maximum Short Circuit Withstand (Icw) |
20.0
| |
Input Total Harmonic Distortion |
Less than 5% for full load
| |
Type of Input Protection Required |
gL fuse
|
Battery Type |
No internal battery - uses external battery system
| |
---|---|---|
Included Battery Modules |
0
| |
Battery Slots Empty |
0
| |
Typical recharge time |
0 hour(s)
| |
RBC Quantity |
0
|
Available SmartSlot™ Interface Quantity |
3
| |
---|---|---|
Pre-Installed SmartSlot™ Cards |
AP9635CH
| |
Control panel |
Multi-function LCD status and control console
| |
Emergency Power Off (EPO) |
Yes
|
Maximum Height |
2210.0 mm
| |
---|---|---|
Maximum Width |
712.0 mm
| |
Maximum Depth |
855.0 mm
| |
Rack Height |
0 U
| |
Net Weight |
488.0 kg
| |
Shipping Weight |
510.0 kg
| |
Shipping Height |
2340.0 mm
| |
Shipping Width |
1080.0 mm
| |
Shipping Depth |
1200.0 mm
| |
Master Carton Units |
1.0
| |
Master Carton Weight |
0.0 lbs
| |
Color |
Light grey
| |
Units per Pallet |
1.0
|
Operating Environment |
0 - 40 °C
| |
---|---|---|
Operating Relative Humidity |
0 - 95 %
| |
Operating Elevation |
0-999.9 meters
| |
Storage Temperature |
-20 - 45 °C
| |
Storage Relative Humidity |
0 - 95 %
| |
Storage Elevation |
0-3600 meters
| |
Audible noise at 1 meter from surface of unit |
65.000 dB
|
Approvals |
CE , EN/IEC 62040-1 , EN/IEC 62040-2 , EN/IEC 62040-3 , IEC 62040-2 , ISO 9001 , TUV , VDE
| |
---|---|---|
Standard warranty |
1 year (parts only) , 1 year on-site repair or replace with factory authorized Start-Up
|