You can choose another country to view available products or go to our Global website for company information.
range of product |
Advantys FTB
| |
---|---|---|
product or component type |
IP67 monobloc I/O splitter box
| |
enclosure material |
Plastic
| |
bus type |
CANopen
| |
input/output number |
16
| |
discrete input number |
12
| |
discrete output number |
4
| |
structure type |
According to EN 50325According to ISO 11898
|
[Ue] rated operational voltage |
24 V DC
| |
---|---|---|
supply current |
8 A
| |
internal current consumption |
120 mA
| |
discrete input voltage |
24 V
| |
discrete input voltage type |
DC
| |
discrete input current |
<= 200 mA
| |
discrete input logic |
Positive
| |
product compatibility |
With 2-wire/3-wire sensors
| |
discrete output voltage |
24 V
| |
discrete output voltage type |
DC
| |
discrete output current |
1600 mA
| |
discrete output type |
Transistor
| |
sensor power supply |
18...30 V
| |
reverse polarity protection |
Internal
| |
switching frequency |
<= 20 Hz
| |
tungsten load |
<= 10 W
| |
electrical connection |
1 female connector 7/8" power OUT1 female connector M12 bus OUT1 male connector 7/8" power IN1 male connector M12 bus IN8 female connectors M12 sensor or actuator
| |
output connection cable size |
0.34 mm², cable length = 5 m0.75 mm², cable length = 10 m
| |
method of access |
Priority informationMultimaster
| |
transmission rate |
1 Mbit/s
| |
transmission support medium |
2 twisted shielded wires
| |
number of addresses |
1...127
| |
input/output number of splitter box |
4 I + 4 O + 8 diagnostic inputs
| |
output overvoltage protection |
Suppressor diode
| |
protection type |
Short-circuit protection
| |
input filtering |
1 ms
| |
control threshold undervoltage |
0...18 V
| |
status LED |
1 LED for actuator power supply diagnostics1 LED for sensor power supply diagnostics1 LED per channel for channel diagnostic1 LED per channel for channel status2 LEDs for bus diagnostic
| |
surge withstand |
-1 kV power supply (asymmetrical) conforming to IEC 61000-4-51 kV power supply (asymmetrical) conforming to IEC 61000-4-5-1 kV signal (asymmetrical) conforming to IEC 61000-4-51 kV signal (asymmetrical) conforming to IEC 61000-4-50.5 kV ground/PE conforming to IEC 61000-4-50.5 kV power supply (symmetrical) conforming to IEC 61000-4-50.5 kV signal (symmetrical) conforming to IEC 61000-4-5
| |
operating position |
Any position
| |
fixing mode |
By 2 screws
| |
tightening torque |
1.5 N.m for M4 screw(s)
| |
product weight |
0.45 kg
|
standards |
IEC 1131-2 Type 2
| |
---|---|---|
product certifications |
cULus
| |
ambient air temperature for operation |
0...55 °C
| |
ambient air temperature for storage |
-25...70 °C
| |
IP degree of protection |
IP67 conforming to IEC 60529
| |
operating altitude |
0...2000 m
| |
vibration resistance |
0.35 mm constant amplitude at 10...57 Hz conforming to IEC 68-2-6, FC test5 gn constant acceleration at 57...150 Hz conforming to IEC 68-2-6, FC test
| |
shock resistance |
30 gn, for 11 ms conforming to IEC 68-2-27, EA tests
| |
resistance to electrostatic discharge |
-4 kV in contact conforming to IEC 61000-4-24 kV in contact conforming to IEC 61000-4-2-8 kV in air conforming to IEC 61000-4-28 kV in air conforming to IEC 61000-4-2
| |
resistance to radiated fields |
10 V/m conforming to IEC 61000-4-3
| |
resistance to fast transients |
-2 kV power supply conforming to IEC 61000-4-42 kV power supply conforming to IEC 61000-4-4-2 kV signal conforming to IEC 61000-4-42 kV signal conforming to IEC 61000-4-4
| |
resistance to conducted disturbances |
10 V conforming to IEC 61000-4-6
|
Warranty period |
18 months
|
---|