You can choose another country to view available products or go to our Global website for company information.
range |
EasyPact
| |
---|---|---|
range of product |
EasyPact
| |
product name |
EasyPact EZC
| |
product or component type |
Circuit breaker
| |
device short name |
Easypact EZC100F
| |
circuit breaker name |
Easypact EZC100F
| |
device application |
Distribution
| |
poles description |
3P
| |
protected poles description |
3t
| |
network type |
ACDC
| |
network frequency |
50/60 Hz
| |
[In] rated current |
100 A ( 40 °C )
| |
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
| |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
| |
[Ue] rated operational voltage |
250 V DC conforming to IEC 60947-2550 V AC 50/60 Hz conforming to IEC 60947-2
| |
breaking capacity code |
F
| |
breaking capacity |
25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-25 kA Icu at 125 V DC 1P conforming to IEC 60947-25 kA Icu at 250 V DC 2P conforming to IEC 60947-25 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-27.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
| |
[Ics] rated service breaking capacity |
Ics 5 kA 380 V AC 50/60 Hz conforming to IEC 60947-2Ics 5 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2Ics 12.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2Ics 12.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2Ics 2.5 kA 125 V DC conforming to IEC 60947-2Ics 2.5 kA 250 V DC conforming to IEC 60947-2Ics 2.5 kA 550 V AC 50/60 Hz conforming to IEC 60947-2Ics 3.75 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
| |
suitability for isolation |
Yes conforming to IEC 60947-2
| |
utilisation category |
Category A
| |
trip unit name |
TM-D
| |
trip unit technology |
Thermal-magnetic
| |
trip unit rating |
100 A ( 50 °C )
| |
protection type |
Overload protectionShort-circuit protection
| |
pollution degree |
3 conforming to IEC 60664-13 conforming to IEC 947-1
|
control type |
Toggle
| |
---|---|---|
mounting mode |
Fixed
| |
mounting support |
Backplate
| |
upside connection |
Front
| |
downside connection |
Front
| |
mechanical durability |
8500 cycles
| |
electrical durability |
Category A : 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
| |
connection pitch |
25 mm
| |
local signalling |
Positive contact indication
| |
neutral protection setting |
Without protection
| |
earth-leakage protection |
Without
| |
height |
130 mm
| |
width |
75 mm
| |
depth |
60 mm
| |
market segment |
Small commercial
| |
compatibility code |
EZC100
|
standards |
EN/IEC 60947-1EN/IEC 60947-2JIS C8201-2-2GB/T 14048.2
| |
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
| |
IK degree of protection |
IK07 conforming to IEC 62262
| |
ambient air temperature for operation |
-25...70 °C
| |
ambient air temperature for storage |
-35...85 °C
|
Warranty period |
18 months
|
---|