  • Reason for Substitution: End of life
  • Substitution date: 30 January 2013
  • -
  • Main
    range of product
    PowerLogic
    device short name
    CM4250
    product or component type
    Circuit monitor
    Complementary
    power quality analysis
    Disturbance direction detection
    Programmablity (logic and math functions)
    Up to the 255th harmonic
    EN 50160 compliance checking
    Harmonic distortion
    Setpoint learning
    Waveform capture
    Voltage sag and swell detection
    device application
    Flicker
    type of measurement
    Active power, total
    Active power, per phase
    Apparent power, total
    Apparent power, per phase
    Power factor, total
    Power factor, per phase
    Reactive power, total
    Reactive power, per phase
    Voltage
    Current
    Frequency
    supply voltage
    100...300 V, DC, 50/60 Hz
    90...305 V, AC,
    network frequency
    50/60 Hz
    power consumption in VA
    <= 50 VA
    sampling rate
    512 samples/cycle
    input type
    Current
    measurement current
    5 A
    measurement voltage
    0...1200 V, AC, with external VT, 0...1.5 Un
    0...690 V, AC, direct, 0...1.5 Un
    measurement accuracy
    Current: 0.025 %, (full scale)
    Current: 0.04 %, (reading)
    Frequency: 0.01 Hz, 45...67 Hz
    Frequency: 0.1 Hz, 350...450 Hz
    Power: 0.025 %, (full scale)
    Power: 0.075 %, (reading)
    Voltage: 0.025 %, (full scale)
    Voltage: 0.04 %, (reading)
    Power factor: 0.002, from 0.5 leading to 0.5 lagging
    accuracy class
    Class 0.2S, (energy conforming to ANSI C12.20)
    Class 0.2S, (energy conforming to IEC 62053-22)
    number of outputs
    1 pulse
    language
    Polish
    English
    German
    Italian
    Spanish
    French
    communication port protocol
    Modbus
    communication port support
    RS485
    Ethernet RJ45
    RS232
    data recording
    Data logs
    Alarms
    Trending/forecasting
    Time stamping
    Min/max of instantaneous values
    Sequence of event recording
    Event logs
    memory capacity
    32 MB
    Environment
    electromagnetic compatibility
    Conducted and radiated emissions ( level: A),
    Electrostatic discharge immunity test ( level: III),, conforming to IEC 61000-4-2
    Electrical fast transient/burst immunity test ( level: III),, conforming to IEC 61000-4-4
    1.2/50 µs shock waves immunity test ( level: IV),, conforming to IEC 61000-4-5
    Susceptibility to electromagnetic fields ( level: III),, conforming to IEC 61000-4-3
    overvoltage category
    IV
    IP degree of protection
    IP52 conforming to IEC 60529
    relative humidity
    5...95 % 40 °C
    pollution degree
    2
    ambient air temperature for operation
    -25...70 °C
    ambient air temperature for storage
    -40...85 °C
    standards
    CISPR 22
    UL 508
    EN 61010
    width
    235.5 mm
    depth
    133.1 mm
    height
    216.3 mm
    165.6 mm
    product weight
    1.9 kg
    Offer Sustainability
    RoHS (date code: YYWW)
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    User guide
    Date
    Size
    Add to My Documents
    Circuit Monitor Manuel d'installation série 4000 FR (Version 1)
    Circuit Monitor Manuel de référence série 4000 FR (Version 1)
    Catalogue page
    Date
    Size
    Add to My Documents
    Références/PowerLogic System (Version 3.0)
    Date 12/18/06
    Size 765.8 KB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 8/23/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /