variable speed drive ATV71 - 75kW-100HP - 480V - EMC filter-graphic terminal
Show more characteristics >
- Reason for Substitution: End of life
- Substitution date: 03 February 2016

- Reason for Substitution: End of life
- Substitution date: 01 April 2016
-
Characteristics
Main range of product Altivar 71product or component type Variable speed driveproduct specific application Complex, high-power machinescomponent name ATV71motor power kW 75 kW at 380...480 V 3 phasesmotor power hp 100 hp at 380...480 V 3 phasesmotor cable length <= 100 m Shielded cable<= 200 m Unshielded cablepower supply voltage 380...480 V (- 15...10 %)network number of phases 3 phasesline current 137 A for 480 V 3 phases 75 kW / 100 hp167 A for 380 V 3 phases 75 kW / 100 hpEMC filter Integratedassembly style With heat sinkapparent power 109.9 kVA at 380 V 3 phases 75 kW / 100 hpprospective line Isc <= 22 kA, 3 phasesnominal output current 124 A at 2.5 kHz 460 V 3 phases 75 kW / 100 hp160 A at 2.5 kHz 380 V 3 phases 75 kW / 100 hpmaximum transient current 240 A for 60 s 3 phases 75 kW / 100 hp264 A for 2 s 3 phases 75 kW / 100 hpoutput frequency 0.1...500 Hznominal switching frequency 2.5 kHzswitching frequency 1...16 kHz adjustable2.5...16 kHz with derating factorasynchronous motor control profile ENA (Energy adaptation) system for unbalanced loadsFlux vector control (FVC) with sensor (current vector)Sensorless flux vector control (SFVC) (voltage or current vector)Voltage/frequency ratio (2 or 5 points)type of polarization No impedance for ModbusComplementary product destination Asynchronous motorsSynchronous motorspower supply voltage limits 323...528 Vpower supply frequency 50...60 Hz (- 5...5 %)power supply frequency limits 47.5...63 Hzspeed range 1...100 for asynchronous motor in open-loop mode, without speed feedback1...50 for synchronous motor in open-loop mode, without speed feedback1...1000 for asynchronous motor in closed-loop mode with encoder feedbackspeed accuracy +/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode with encoder feedback+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedbacktorque accuracy +/- 15 % in open-loop mode, without speed feedback+/- 5 % in closed-loop mode with encoder feedbacktransient overtorque 220 % of nominal motor torque +/- 10 % for 2 s170 % of nominal motor torque +/- 10 % for 60 s every 10 minutesbraking torque <= 150 % with braking or hoist resistor30 % without braking resistorsynchronous motor control profile Vector control without speed feedbackregulation loop Adjustable PI regulatormotor slip compensation AdjustableAutomatic whatever the loadNot available in voltage/frequency ratio (2 or 5 points)Suppressablediagnostic 1 LED red presence of drive voltageoutput voltage <= power supply voltageinsulation Electrical between power and controltype of cable for mounting in an enclosure With a NEMA Type1 kit : 3-strand UL 508 cable at 40 °C, copper 75 °C PVCWith an IP21 or an IP31 kit : 3-strand IEC cable at 40 °C, copper 70 °C PVCWithout mounting kit : 1-strand IEC cable at 45 °C, copper 70 °C PVCWithout mounting kit : 1-strand IEC cable at 45 °C, copper 90 °C XLPE/EPRelectrical connection AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5 mm² / AWG 14L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 150 mm²tightening torque L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 41 N.m / 360 lb.inAI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 0.6 N.msupply Internal supply for reference potentiometer (1 to 10 kOhm), 10.5 V DC +/- 5 %, <= 10 mA for overload and short-circuit protectionInternal supply, 24 V DC, voltage limits 21...27 V, <= 200 mA for overload and short-circuit protectionanalogue input number 2analogue input type AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution 11 bits + signAI2 software-configurable current 0...20 mA, impedance 242 Ohm, resolution 11 bitsAI2 software-configurable voltage 0...10 V DC, input voltage 24 V max, impedance 30000 Ohm, resolution 11 bitsinput sampling time AI1-/Al1+ 2 ms, +/- 0.5 ms for analog input(s)Al2 2 ms, +/- 0.5 ms for analog input(s)LI1...LI5 2 ms, +/- 0.5 ms for discrete input(s)LI6 (if configured as logic input) 2 ms, +/- 0.5 ms for discrete input(s)response time <= 100 ms in STO (Safe Torque Off)AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)absolute accuracy precision AI1-/Al1+ +/- 0.6 % for a temperature variation 60 °CAI2 +/- 0.6 % for a temperature variation 60 °CAO1 +/- 1 % for a temperature variation 60 °Clinearity error AI1-/Al1+, AI2 +/- 0.15 % of maximum valueAO1 +/- 0.2 %analogue output number 1analogue output type AO1 software-configurable current 0...20 mA, impedance 500 Ohm, resolution 10 bitsAO1 software-configurable logic output 10 V <= 20 mAAO1 software-configurable voltage 0...10 V DC, impedance 470 Ohm, resolution 10 bitsdiscrete output number 2discrete output type R1A, R1B, R1C configurable relay logic NO/NC, electrical durability 100000 cyclesR2A, R2B configurable relay logic NO, electrical durability 100000 cyclesminimum switching current Configurable relay logic 3 mA at 24 V DCmaximum switching current R1, R2 on resistive load, 5 A at 250 V AC, cos phi = 1,R1, R2 on resistive load, 5 A at 30 V DC, cos phi = 1,R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4,R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4,discrete input number 7discrete input type LI6 : switch-configurable 24 V DC with level 1 PLC, impedance: 3500 OhmPWR : safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level dLI1...LI5 : programmable 24 V DC with level 1 PLC, impedance: 3500 OhmLI6 : switch-configurable PTC probe 0...6, impedance: 1500 Ohmdiscrete input logic LI1...LI5 positive logic (source), < 5 V (state 0), > 11 V (state 0)LI1...LI5 negative logic (sink), > 16 V (state 0), < 10 V (state 0)LI6 (if configured as logic input) positive logic (source), < 5 V (state 0), > 11 V (state 0)LI6 (if configured as logic input) negative logic (sink), > 16 V (state 0), < 10 V (state 0)acceleration and deceleration ramps Automatic adaptation of ramp if braking capacity exceeded, by using resistorLinear adjustable separately from 0.01 to 9000 sS, U or customizedbraking to standstill By DC injectionprotection type Drive against exceeding limit speedDrive against input phase lossDrive break on the control circuitDrive input phase breaksDrive line supply overvoltageDrive line supply undervoltageDrive overcurrent between output phases and earthDrive overheating protectionDrive overvoltages on the DC busDrive short-circuit between motor phasesDrive thermal protectionMotor motor phase breakMotor power removalMotor thermal protectioninsulation resistance > 1 mOhm at 500 V DC for 1 minute to earthfrequency resolution Analog input 0.024/50 HzDisplay unit 0.1 Hzcommunication port protocol CANopenModbusconnector type 1 RJ45 for Modbus on front face1 RJ45 for Modbus on terminalMale SUB-D 9 on RJ45 for CANopenphysical interface 2-wire RS 485 for Modbustransmission frame RTU for Modbustransmission rate 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal9600 bps, 19200 bps for Modbus on front facedata format 8 bits, 1 stop, even parity for Modbus on front face8 bits, odd even or no configurable parity for Modbus on terminalnumber of addresses 1...247 for Modbus1...127 for CANopenmethod of access Slave for CANopenmarking CEoperating position Vertical +/- 10 degreeheight 630 mmdepth 290 mmwidth 320 mmproduct weight 44 kgfunctionality Fullspecific application Other applicationsoption card CC-Link communication cardController inside programmable cardDeviceNet communication cardEthernet/IP communication cardFipio communication cardI/O extension cardInterbus-S communication cardInterface card for encoderModbus Plus communication cardModbus TCP communication cardModbus/Uni-Telway communication cardOverhead crane cardProfibus DP communication cardProfibus DP V1 communication cardEnvironment noise level 63.7 dB conforming to 86/188/EECdielectric strength 3535 V DC between earth and power terminals5092 V DC between control and power terminalselectromagnetic compatibility Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 level 3Voltage dips and interruptions immunity test conforming to IEC 61000-4-111.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3standards EN 55011 class A group 2EN 61800-3 environments 1 category C3EN 61800-3 environments 2 category C3EN/IEC 61800-3EN/IEC 61800-5-1IEC 60721-3-3 class 3C1IEC 60721-3-3 class 3S2UL Type 1product certifications CSAC-TickGOSTNOM 117ULpollution degree 2 conforming to EN/IEC 61800-5-13 conforming to UL 840IP degree of protection IP20vibration resistance 1.5 mm peak to peak (f = 3...13 Hz) conforming to EN/IEC 60068-2-61 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27relative humidity 5...95 % without condensation conforming to IEC 60068-2-35...95 % without dripping water conforming to IEC 60068-2-3ambient air temperature for operation -10...50 °C without deratingambient air temperature for storage -25...70 °Coperating altitude <= 1000 m without derating1000...3000 m with current derating 1 % per 100 mOffer Sustainability Sustainable offer status Green Premium productRoHS (date code: YYWW) REACh Product environmental profile Product end of life instructions AvailableContractual warranty Warranty period 18 months -
Documents and Downloads
Language- English
- Spanish
- Russian
- French
- Italian
- Chinese
- German
Software - ReleasedSizeAdd to My DocumentsSoMove V2.6.5 (FDT Standalone) (Version 2.6.5)DTM filesSizeAdd to My DocumentsAltivar DTM Library V12.8: ATV12, ATV31/312, ATV32, ATV61, ATV71, ATV LIFT, ATV212 (Version 12.8)Date 1/11/19Size 422.5 MBDate 1/11/19Size 205.2 KBCatalogueSizeAdd to My DocumentsCatalog: Altivar 71/71 Plus variable speed drives - English version 2014/04 (web pdf format) (Version 1.0)Date 8/10/18Size 10.7 MBCatalogue : variateurs de vitesse Altivar 71/71 Plus - Version française 2014/04 (format PDF web) (Version 1.0)Date 8/10/18Size 14.3 MBUser guideSizeAdd to My DocumentsATV71 Guía de instalación 0,37 - 90 kW (Version 05)ATV71 Installationsanleitung 0,37 - 90 kW (Version 05)ATV71 Guida d’installazione 0,37 - 90 kW (Version 05)ATV71 Installation Manual 0,37 - 90 kW (Version 05)ATV71 Guide d’installation 0,37 - 90 kW (Version 05)ATV71 Quick Start annex: SCCR and branch circuit protection (Version 03)ATV61/71/ LIFT Safety integrated function manual (Version 04)ATV71 Guide de programmation (Version 10)ATV71 Guida alla programmazione (Version 10)CADSizeAdd to My DocumentsPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (Version 1.1)Power 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dwf)Date 4/25/17Size 7 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dwg)Date 4/25/17Size 170.9 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dxf)Date 4/25/17Size 446.9 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (wmf)Date 4/25/17Size 59.9 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (Version 1.1)Power 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dwf)Date 4/25/17Size 11.5 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dwg)Date 4/25/17Size 263.5 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (dxf)Date 4/25/17Size 724.2 KBPower 45 to 75 KW single phase or 3 phase supply voltage 200 to 480 V graphic display terminal (wmf)Date 4/25/17Size 217.4 KBCertificateSizeAdd to My DocumentsE116875 UL GENERIC CERTIFICATE (Version 1.0)ATV61-71 H-W CSA CERTIFICATE (Version 1.0)Instruction sheetSizeAdd to My DocumentsInstruction Sheet - Migration Plate ATV61-71 to ATV600-ATV900 : VW3A93111... VW3A93120 (Version 01)Date 11/19/18Size 169.6 KBMarine certificateSizeAdd to My DocumentsLR Marine Certificate ATV71 Altivar VSD (Version 1.0)DNV-GL Marine Certificate ATV71 variable speed drives (Version 1.0)Product Environmental ProfileSizeAdd to My DocumentsPEP Altivar 71 (18,5 to 75 kW) (Version 1.1) -
Technical FAQs
No results found.Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later. -
Dimensions Drawings
UL Type 1/IP 20 DrivesDimensions without Option CardDimensions with 1 Option Card (1)(1) Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card.
Dimensions with 2 Option Cards (1)(1) Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card.
-
Mounting and Clearance
Mounting RecommendationsDepending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories.
Install the unit vertically:
Avoid placing it close to heating elements
Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
ClearanceMounting TypesType A Mounting
Type B Mounting
Type C Mounting
By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20.
The protective blanking cover may vary according to the drive model (refer to the user guide).
The protective blanking cover must be removed from ATV 71P•••N4Z drives when they are mounted in a dust and damp proof enclosure.
Specific Recommendations for Mounting the Drive in an EnclosureVentilationTo ensure proper air circulation in the drive:
Fit ventilation grilles.
Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).
Use special filters with IP 54 protection.
Remove the blanking cover from the top of the drive.
Dust and Damp Proof Metal Enclosure (IP 54)The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions: dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.
This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
-
Connections and Schema
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category 0 According to IEC/EN 60204-1Three-Phase Power Supply with Upstream Breaking via ContactorA1ATV71 driveKM1ContactorL1DC chokeQ1Circuit-breakerQ2GV2 L rated at twice the nominal primary current of T1Q3GB2CB05S1, S2XB4 B or XB5 A pushbuttonsT1100 VA transformer 220 V secondary(1)Line choke (three-phase); mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).(2)For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram.(3)Fault relay contacts. Used for remote signalling of the drive status.(4)Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “source” position (for other connection types, refer to the user guide).(5)There is no PO terminal on ATV71HC11Y…HC63Y drives.(6)Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it.(7)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.(8)Reference potentiometer.All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category 0 According to IEC/EN 60204-1Three-Phase Power Supply with Downstream Breaking via Switch DisconnectorA1ATV71 driveL1DC chokeQ1Circuit-breakerQ2Switch disconnector (Vario)(1)Line choke (three-phase), mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).(2)For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram.(3)Fault relay contacts. Used for remote signalling of the drive status.(4)Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “source” position (for other connection types, refer to the user guide).(5)There is no PO terminal on ATV71HC11Y…HC63Y drives.(6)Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it.(7)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.(8)Reference potentiometer.All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping Category 0 According to IEC/EN 60204-1Three-Phase Power Supply, Low Inertia Machine, Vertical MovementA1ATV71 driveA2Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the “Power Removal” function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24 V via the safety contacts on the XPS AC module. These contacts are independent for each drive.F1FuseL1DC chokeQ1Circuit-breakerS1Emergency stop button with 2 contactsS2XB4 B or XB5 A pushbutton(1)Power supply: 24 Vdc or Vac, 48 Vac, 115 Vac, 230 Vac.(2)S2: resets XPS AC module on power-up or after an emergency stop. ESC can be used to set external starting conditions.(3)Requests freewheel stopping of the movement and activates the “Power Removal” safety function.(4)Line choke (three-phase), mandatory for and ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).(5)The logic output can be used to signal that the machine is in a safe stop state.(6)For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram.(7)Fault relay contacts. Used for remote signalling of the drive status.(8)Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “source” position (for other connection types, refer to the user guide).(9)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed.(10)There is no PO terminal on ATV71HC11Y…HC63Y drives.(11)Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it.(12)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.(13)Reference potentiometer.All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping Category 1 According to IEC/EN 60204-1Three-Phase Power Supply, High Inertia MachineA1ATV71 driveA2 (5)Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal” safety function for several drives on the same machine. In this case the time delay must be adjusted on the drive controlling the motor that requires the longest stopping time. In addition, each drive must connect its PWR terminal to its + 24 V via the safety contacts on the XPS ATE module. These contacts are independent for each drive.F1FuseL1DC chokeQ1Circuit-breakerS1Emergency stop button with 2 N/C contactsS2Run button(1)Power supply: 24 Vdc or Vac, 115 Vac, 230 Vac.(2)Requests controlled stopping of the movement and activates the “Power Removal” safety function.(3)Line choke (three-phase), mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).(4)S2: resets XPS ATE module on power-up or after an emergency stop. ESC can be used to set external starting conditions.(5)For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a maximum time delay of 300 seconds.(6)The logic output can be used to signal that the machine is in a safe state.(7)For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram.(8)Fault relay contacts. Used for remote signalling of the drive status.(9)Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “source” position (for other connection types, refer to the user guide).(10)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm/0.09 in., maximum length 15 m/49.21 ft. The cable shielding must be earthed.(11)Logic inputs LI1 and LI2 must be assigned to the direction of rotation: LI1 in the forward direction and LI2 in the reverse direction.(12)There is no PO terminal on ATV71HC11Y…HC63Y drives.(13)Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it.(14)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.(15)Reference potentiometer.All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
-
Performance Curves
Derating CurvesThe derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For intermediate temperatures (e.g. 55°C), interpolate between 2 curves.
XSwitching frequency(1)Mounting typeAbove 50ºC, the drive should be fitted with a control card fan kit.