Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric ATV61QC25N4 Image

Range: Altivar 61Q

Variable speed drives

ATV61QC25N4

Schneider Electric ATV61QC25N4 Image
Range: Altivar 61Q

Variable speed drives

ATV61QC25N4

variable speed drive ATV61Q - 250kW / 400HP - 380...480V - IP20

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Altivar 61Q
    product or component type
    Variable speed drive
    device short name
    ATV61Q
    product destination
    Asynchronous motors
    Synchronous motors
    product specific application
    Pumping and ventilation machine
    assembly style
    With heat sink
    EMC filter
    Integrated
    network number of phases
    3 phases
    [Us] rated supply voltage
    380...480 V (- 15...10 %)
    supply voltage limits
    323...528 V
    supply frequency
    50...60 Hz (- 5...5 %)
    network frequency limits
    47.5...63 Hz
    motor power kW
    250 kW 3 phases for 380...480 V
    motor power hp
    400 hp 3 phases for 380...480 V
    motor cable length
    <= 100 m shielded cable without motor choke
    <= 200 m unshielded cable without motor choke
    <= 250 m unshielded cable with motor choke
    <= 200 m shielded cable with motor choke
    line current
    435 A for 480 V 3 phases / 250 kW / 400 hp
    444 A for 380 V 3 phases / 250 kW / 400 hp
    Complementary
    apparent power
    292.2 kVA for 380 V 3 phases / 250 kW / 400 hp
    prospective line Isc
    50 kA for 3 phases
    continuous output current
    481 A at 2.5 kHz, 380 V - 3 phases
    481 A at 2.5 kHz, 460 V - 3 phases
    maximum transient current
    577.2 A for 60 s - 3 phases
    speed drive output frequency
    0.1...500 Hz
    nominal switching frequency
    2.5 kHz
    switching frequency
    2...8 kHz adjustable
    2.5...8 kHz with derating factor
    speed range
    1...100 in open-loop mode, without speed feedback
    speed accuracy
    +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation, without speed feedback
    torque accuracy
    +/- 15 % in open-loop mode, without speed feedback
    transient overtorque
    130 % of nominal motor torque, +/- 10 % for 60 s
    braking torque
    30 % without braking resistor
    <= 125 % with braking resistor
    asynchronous motor control profile
    Voltage/frequency ratio, 2 points
    Voltage/frequency ratio, 5 points
    Flux vector control without sensor, standard
    Voltage/frequency ratio - Energy Saving, quadratic U/f
    synchronous motor control profile
    Vector control without sensor, standard
    regulation loop
    Frequency PI regulator
    motor slip compensation
    Adjustable
    Automatic whatever the load
    Can be suppressed
    Not available in voltage/frequency ratio (2 or 5 points)
    local signalling
    1 LED - red - drive voltage
    output voltage
    <= power supply voltage
    isolation
    Between power and control terminals
    type of cable
    IEC cable without mounting kit : 1 wire(s) - 45 °C, copper 90 °C / XLPE/EPR
    IEC cable without mounting kit : 1 wire(s) - 45 °C, copper 70 °C / PVC
    UL 508 cable with UL Type 1 kit : 3 wire(s) - 40 °C, copper 75 °C / PVC
    IEC cable with an IP21 or an IP31 kit : 3 wire(s) - 40 °C, copper 70 °C / PVC
    electrical connection
    Terminal 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
    Terminal 4 x 185 mm² / 3 x 350 kcmil (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
    Terminal 4 x 185 mm² / 3 x 350 kcmil (PC/-, PO, PA/+)
    tightening torque
    0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
    41 N.m, 360 lb.in (PC/-, PO, PA/+)
    41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
    supply
    External supply : 24 V DC (19...30 V) - 30 W
    Internal supply : 24 V DC (21...27 V) - <= 200 mA with overload and short-circuit protection
    Internal supply for reference potentiometer (1 to 10 kOhm) : 10.5 V DC, +/- 5 % - <= 10 mA with overload and short-circuit protection
    analogue input number
    2
    analogue input type
    Software-configurable current : (AI2) 0...20 mA - 242 Ohm - resolution: 11 bits
    Software-configurable voltage : (AI2) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 11 bits
    Bipolar differential voltage : (AI1-/Al1+) +/- 10 V DC - 24 V max - resolution: 11 bits + sign
    sampling duration
    2 ms +/- 0.5 ms (AI1-/Al1+) for analog input
    2 ms +/- 0.5 ms (Al2) for analog input
    2 ms +/- 0.5 ms (AO1) for analog output
    2 ms +/- 0.5 ms (LI1...LI5) for discrete input
    2 ms +/- 0.5 ms (LI6) if configured as logic input for discrete input
    accuracy
    +/- 1 % (AO1) for a temperature variation 60 °C
    +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
    +/- 0.6 % (AI2) for a temperature variation 60 °C
    linearity error
    +/- 0.2 % (AO1)
    +/- 0.15 % of maximum value (AI1-/Al1+)
    +/- 0.15 % of maximum value (AI2)
    analogue output number
    1
    analogue output type
    Software-configurable current : (AO1) 0...20 mA - 500 Ohm - resolution: 10 bits
    Software-configurable voltage : (AO1) 0...10 V DC - 470 Ohm - resolution: 10 bits
    Software-configurable logic output : (AO1) 10 V - <= 20 mA
    discrete output number
    2
    discrete output type
    Configurable relay logic : (R1A, R1B, R1C) NO/NC - 100000 cycles
    Configurable relay logic : (R2A, R2B) NO - 100000 cycles
    response time
    <= 100 ms in STO (Safe Torque Off)
    <= 7 ms +/- 0.5 ms (R1A, R1B, R1C)
    <= 7 ms +/- 0.5 ms (R2A, R2B)
    minimum switching current
    3 mA at 24 V DC (configurable relay logic)
    maximum switching current
    5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (R1, R2)
    5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (R1, R2)
    2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1, R2)
    2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1, R2)
    discrete input number
    7
    discrete input type
    Switch-configurable PTC probe (LI6) - 0...6 probes - 1500 Ohm
    Programmable (LI1...LI5) 24 V DC, with level 1 PLC - 3500 Ohm
    Switch-configurable (LI6) 24 V DC, with level 1 PLC - 3500 Ohm
    Safety input (PWR) 24 V DC - 1500 Ohm
    discrete input logic
    Negative logic (sink) (LI1...LI5) , > 16 V (state 0), < 10 V (state 1)
    Positive logic (source) (LI1...LI5) , < 5 V (state 0), > 11 V (state 1)
    Negative logic (sink) (LI6) if configured as logic input, > 16 V (state 0), < 10 V (state 1)
    Positive logic (source) (LI6) if configured as logic input, < 5 V (state 0), > 11 V (state 1)
    acceleration and deceleration ramps
    Automatic adaptation of ramp if braking capacity exceeded, by using resistor
    Linear adjustable separately from 0.01 to 9000 s
    S, U or customized
    braking to standstill
    By DC injection
    protection type
    Overheating protection for drive
    Thermal protection for drive
    Short-circuit between motor phases for drive
    Overcurrent between output phases and earth for drive
    Overvoltages on the DC bus for drive
    Break on the control circuit for drive
    Against exceeding limit speed for drive
    Line supply undervoltage for drive
    Line supply overvoltage for drive
    Against input phase loss for drive
    Thermal protection for motor
    Motor phase break for motor
    Power removal for drive
    Input phase breaks for drive
    Power removal for motor
    dielectric strength
    3535 V DC between earth and power terminals
    5092 V DC between control and power terminals
    insulation resistance
    > 1 mOhm at 500 V DC for 1 minute to earth
    frequency resolution
    0.1 Hz for display unit
    0.024/50 Hz for analog input
    communication port protocol
    CANopen
    Modbus
    connector type
    1 RJ45 for Modbus on front face
    1 RJ45 for Modbus on terminal
    Male SUB-D 9 on RJ45 for CANopen
    physical interface
    2-wire RS 485 for Modbus
    transmission frame
    RTU for Modbus
    transmission rate
    20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
    4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
    9600 bps, 19200 bps for Modbus on front face
    data format
    8 bits, 1 stop, even parity for Modbus on front face
    8 bits, odd even or no configurable parity for Modbus on terminal
    type of polarization
    No impedance for Modbus
    number of addresses
    1...247 addresses for Modbus
    1...127 addresses for CANopen
    method of access
    Slave for CANopen
    type of cooling
    Water cooled
    cooling fluid type
    Water-glycol mixture
    Clean water
    Industrial water
    operating temperature water
    5...55 °C
    thermal losses
    5000 W 100 % of line current for area of liquid cooling (power part)
    1030 W 100 % of line current for area of air cooling (control part)
    flow velocity
    24
    pressure drop
    < 1 bar
    volume of cooling water
    0.4 l
    operating position
    Vertical +/- 10 degree
    product weight
    140 kg
    option card
    Controller inside programmable card
    I/O extension card
    Multi-pump card
    Communication card for Profibus DP
    Communication card for Modbus TCP
    Communication card for Fipio
    Communication card for Modbus/Uni-Telway
    Communication card for Modbus Plus
    Communication card for Ethernet/IP
    Communication card for DeviceNet
    Communication card for Profibus DP V1
    Communication card for Interbus-S
    Communication card for CC-Link
    Communication card for LonWorks
    Communication card for METASYS N2
    Communication card for APOGEE FLN
    Communication card for BACnet
    width
    585 mm
    height
    950 mm
    depth
    377 mm
    Environment
    ambient air temperature for operation
    -10...50 °C without derating
    50...60 °C with derating factor
    ambient air temperature for storage
    -25...70 °C
    operating altitude
    <= 1000 m without derating
    1000...3000 m with current derating 1 % per 100 m
    electromagnetic compatibility
    Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
    Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
    Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
    Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
    pollution degree
    3 conforming to EN/IEC 61800-5-1
    3 conforming to UL 840
    IP degree of protection
    IP00 conforming to EN/IEC 60529
    IP00 conforming to EN/IEC 61800-5-1
    IP30 on side parts conforming to EN/IEC 60529
    IP30 on side parts conforming to EN/IEC 61800-5-1
    IP30 on the front panel conforming to EN/IEC 60529
    IP30 on the front panel conforming to EN/IEC 61800-5-1
    IP41 on upper part conforming to EN/IEC 60529
    IP41 on upper part conforming to EN/IEC 61800-5-1
    IP54 on lower part conforming to EN/IEC 60529
    IP54 on lower part conforming to EN/IEC 61800-5-1
    vibration resistance
    1.5 mm peak to peak (f = 3...10 Hz) conforming to EN/IEC 60068-2-6
    0.6 gn (f = 10...200 Hz) conforming to EN/IEC 60068-2-6
    shock resistance
    4 gn for 11 ms conforming to EN/IEC 60068-2-27
    relative humidity
    5...95 % without condensation conforming to IEC 60068-2-3
    5...95 % without dripping water conforming to IEC 60068-2-3
    noise level
    68 dB conforming to 86/188/EEC
    standards
    EN 55011 class A group 2
    EN 61800-3 environments 1 category C3
    EN 61800-3 environments 2 category C3
    EN/IEC 61800-3
    EN/IEC 61800-5-1
    IEC 60721-3-3 class 3C2
    UL Type 1
    product certifications
    CSA
    C-Tick
    DNV
    GOST
    NOM 117
    UL
    marking
    CE
    Offer Sustainability
    RoHS (date code: YYWW)
    REACh
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Russian
    • French
    • Italian
    • Chinese
    • German
    Software - Released
    Date
    Size
    Add to My Documents
    SoMove V2.6.5 (FDT Standalone)
    Date 6/19/18
    Size 234.4 MB
    Date 6/19/18
    Size 107.1 KB
    DTM files
    Date
    Size
    Add to My Documents
    Altivar DTM Library V12.8: ATV12, ATV31/312, ATV32, ATV61, ATV71, ATV LIFT, ATV212
    Catalogue
    Date
    Size
    Add to My Documents
    User guide
    Date
    Size
    Add to My Documents
    Date 12/14/17
    Size 180.5 KB
    Date 4/25/14
    Size 8.1 MB
    Date 2/14/18
    Size 4.4 MB
    Date 4/25/14
    Size 8.2 MB
    Date 4/25/14
    Size 7.5 MB
    Date 4/25/14
    Size 7.5 MB
    CAD
    Date
    Size
    Add to My Documents
    Date 9/23/17
    Size 5.3 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 4/27/18
    Size 2.1 MB
    Date 7/18/18
    Size 1.7 MB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions
    Without or with 1 option card


    With 2 option cards



  • Mounting and Clearance

    Clearance



    Wall-Mounting

    The drive is designed for installation on the wall, in an electrical room or into an enclosure. The device is built according to pollution degree 2. If the environment does not correspond to these conditions then the necessary transition of the pollution degree must be provided e.g. by means of an enclosure.


    (1)
    Drive
    (2)
    Cooling water inlet
    (3)
    Cooling water return
    (4)
    Cooling air for control part
    (5)
    Cooling air for power part (only capacitors)


  • Connections and Schema

    Wiring Diagram


    A1
    Drive
    BU
    Braking Unit
    F1
    Fast-acting semi-conductor fuse
    IL1
    Line choke
    KM1
    Optional line contactor
    M
    Motor
    Q1
    Switch
    RFI
    Optional radio frequency interference filter
    (1)
    Filter
    (2)
    Control
    (3)
    Relay control
    (4)
    Control potentiometer
    (5)
    PLC
    (6)
    External optional braking resistor
    (7)
    Optional motor choke


  • Performance Curves

    Continuous Current at Output Frequencies < 1 Hz

    Due to the especially efficient liquid cooling of the drive a high overload capability is also available in the speed range of < 1 Hz.


    (1)
    Continuous operation: 120% overload capability
    (2)
    Overload 120% for 60 s


    Power Derating

    4 kHz pulse frequency

    +5°K air temperature

    8%

    10%