  • Main
    range of product
    Altistart 22
    product or component type
    Soft starter
    product destination
    Asynchronous motors
    product specific application
    Pumps and fans
    component name
    ATS22
    network number of phases
    3 phases
    [Us] rated supply voltage
    230...440 V - 15...10 %
    motor power kW
    39 kW 230 V
    55 kW 400 V
    55 kW 440 V
    factory setting current
    100 A
    power dissipation in W
    73 W for standard applications
    utilisation category
    AC-53A
    type of start
    Start with torque control (current limited to 3.5 In)
    IcL starter rating
    110 A connection in the motor supply line for standard applications
    IP degree of protection
    IP20
    Complementary
    assembly style
    With heat sink
    function available
    Internal bypass
    supply voltage limits
    195...484 V
    supply frequency
    50...60 Hz - 10...10 %
    network frequency
    45...66 Hz
    device connection
    To the motor delta terminals
    In the motor supply line
    [Uc] control circuit voltage
    230 V -15...10 % 50/60 Hz
    control circuit consumption
    20 W
    discrete output number
    2
    discrete output type
    Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
    Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
    minimum switching current
    100 mA 12 V DC relay outputs
    maximum switching current
    5 A 250 V AC resistive 1 relay outputs
    5 A 30 V DC resistive 1 relay outputs
    2 A 250 V AC inductive 0.4 20 ms relay outputs
    2 A 30 V DC inductive 7 ms relay outputs
    discrete input number
    3
    discrete input type
    Logic LI1, LI2, LI3 5 mA 4.3 kOhm
    discrete input voltage
    24 V <= 30 V
    discrete input logic
    Positive logic LI1, LI2, LI3 < 5 V and <= 2 mA > 11 V >= 5 mA
    output current
    0.4...1 Icl adjustable
    PTC probe input
    750 Ohm
    communication port protocol
    Modbus
    connector type
    1 RJ45
    communication data link
    Serial
    physical interface
    RS485 multidrop
    transmission rate
    4800, 9600 or 19200 bps
    installed device
    31
    protection type
    Phase failure line
    Thermal protection starter
    Thermal protection motor
    marking
    CE
    type of cooling
    Forced convection
    operating position
    Vertical +/- 10 degree
    height
    356 mm
    width
    150 mm
    depth
    229.5 mm
    product weight
    18 kg
    Motor power range AC-3
    30...50 kW at 200...240 V 3 phases
    55...100 kW at 380...440 V 3 phases
    motor starter type
    Soft starter
    Environment
    electromagnetic compatibility
    Conducted and radiated emissions level A IEC 60947-4-2
    Damped oscillating waves level 3 IEC 61000-4-12
    Electrostatic discharge level 3 IEC 61000-4-2
    Immunity to electrical transients level 4 IEC 61000-4-4
    Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
    Voltage/current impulse level 3 IEC 61000-4-5
    standards
    EN/IEC 60947-4-2
    product certifications
    C-Tick
    GOST
    UL
    CCC
    CSA
    vibration resistance
    1.5 mm 2...13 Hz EN/IEC 60068-2-6
    1 gn 13...200 Hz EN/IEC 60068-2-6
    shock resistance
    15 gn 11 ms EN/IEC 60068-2-27
    noise level
    56 dB
    pollution degree
    Level 2 IEC 60664-1
    relative humidity
    0...95 % without condensation or dripping water EN/IEC 60068-2-3
    ambient air temperature for operation
    -10...40 °C without derating
    > 40...< 60 °C with current derating 2.2 % per °C
    ambient air temperature for storage
    -25...70 °C
    operating altitude
    <= 1000 m without derating
    > 1000...< 2000 m with current derating of 2.2 % per additional 100 m
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0938  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • French
    • Italian
    • Chinese
    • German
    • Turkish
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue: Démarreurs-ralentisseurs Altistart 22 (Version 2.0)
    Catalog: Soft start/soft stop units Altistart 22 (Version 2.0)
    User guide
    Date
    Size
    Add to My Documents
    ATS22 User manual (Version 04)
    Date 9/13/15
    Size 5.6 MB
    ATS22 Benutzerhandbuch (Version 04)
    Date 9/30/15
    Size 5.7 MB
    ATS22 Guide d'exploitation (Version 04)
    Date 9/30/15
    Size 2.9 MB
    1) ATS22 - Kurzanleitung (Version 04)
    Date 8/30/12
    Size 461.2 KB
    1) ATS22 - Guide de démarrage rapide (Version 04)
    1) ATS22 - Quick Start guide (Version 04)
    Date 8/30/12
    Size 467.5 KB
    1) ATS22 Guida rapida (Version 04)
    Date 8/30/12
    Size 461.8 KB
    1) ATS22 - Guía de arranque rápido (Version 04)
    1) ATS22 - 快速入门指南 (Version 04)
    Date 8/30/12
    Size 616.6 KB
    ATS22 用户手册 (Version 04)
    Date 9/30/15
    Size 5.8 MB
    ATS22 Manuale d'uso (Version 04)
    Date 9/30/15
    Size 2.8 MB
    ATS22 Manual del usuario (Version 04)
    Date 9/30/15
    Size 2.9 MB
    CAD
    Date
    Size
    Add to My Documents
    CAD file (on TraceParts) for ATS22C11Q: soft starter-ATS22-control 220V-power 230V(39kW)/400...440V(55kW) (Version 2.0)
    Certificate
    Date
    Size
    Add to My Documents
    ATS22 CSA CERTIFICATE (Version 1.0)
    Date 10/22/12
    Size 69.4 KB
    ATS22 EU DECLARATION (Version 1.0)
    Date 4/20/16
    Size 399.4 KB
    ATS22 UL CERTIFICATE (Version 1.0)
    Date 1/4/11
    Size 153 KB
    DTM files
    Date
    Size
    Add to My Documents
    Altistart DTM Library V12.0.0 (ATS22, ATS48) (Version 12.0.0)
    End of Life Information
    Date
    Size
    Add to My Documents
    ALTISTART 22, 55 – 90 kW, Product End-of-Life Instructions (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    Product Environmental Profile Altistart 22 Range: 55 to 90 kW (Version 1.1)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Software - Released
    Date
    Size
    Add to My Documents
    SoMove V2.7.5 (FDT Standalone) (Version 2.7.5)
    Date 6/6/19
    Size 281.2 MB
    Date 6/6/19
    Size 108.1 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /