Welcome to the Schneider Electric corporate Website

ENGLISH | FRENCH

You can choose another country to view available products or go to our Global website for company information.

Choose your country or region

Schneider Electric ATS01N222QN Image

Range: Motor Starter Components Finder

Products for Motor protection and control

ATS01N222QN

Schneider Electric ATS01N222QN Image
Range: Motor Starter Components Finder

Products for Motor protection and control

ATS01N222QN

soft starter for asynchronous motor - ATS01 - 22 A - 380..415V - 7.5..11 KW

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Altistart 01
    product or component type
    Soft starter
    product destination
    Asynchronous motors
    product specific application
    Simple machine
    device short name
    ATS01
    network number of phases
    3 phases
    [Us] rated supply voltage
    380...415 V - 10...10 %
    motor power kW
    11 kW 3 phases 380...415 V
    7.5 kW 3 phases 380...415 V
    IcL starter rating
    22 A
    utilisation category
    AC-53B EN/IEC 60947-4-2
    current consumption
    110 A at nominal load
    type of start
    Start with voltage ramp
    power dissipation in W
    124.5 W in transient state
    4.5 W at full load and at end of starting
    Complementary
    assembly style
    With heat sink
    function available
    Integrated bypass
    supply voltage limits
    342...456 V
    supply frequency
    50...60 Hz - 5...5 %
    network frequency
    47.5...63 Hz
    output voltage
    <= power supply voltage
    [Uc] control circuit voltage
    Built into the starter
    starting time
    1 s 100
    10 s 10
    5 s 20
    Adjustable from 1 to 10 s
    deceleration time symb
    Adjustable from 1 to 10 s
    starting torque
    30...80 % of starting torque of motor connected directly on the line supply
    discrete input type
    Logic LI1, LI2, BOOST stop, run and boost on start-up functions <= 8 mA 27 kOhm
    discrete input voltage
    24...40 V
    discrete input logic
    Positive LI1, LI2, BOOST < 5 V and <= 0.2 mA > 13 V >= 0.5 mA
    discrete output current
    2 A DC-13
    3 A AC-15
    discrete output type
    Open collector logic LO1 end of starting signal
    Relay outputs R1A, R1C NO
    discrete output voltage
    24 V 6...30 V open collector logic
    minimum switching current
    10 mA 6 V DC relay outputs
    maximum switching current
    2 A 250 V AC inductive cos phi = 0.5 20 ms relay outputs
    2 A 30 V DC inductive cos phi = 0.5 20 ms relay outputs
    display type
    1 LED green starter powered up
    1 LED yellow nominal voltage reached
    tightening torque
    0.5 N.m
    1.9...2.5 N.m
    electrical connection
    4 mm screw clamp terminal rigid 1 1...10 mm² AWG 8 power circuit
    Screw connector rigid 1 0.5...2.5 mm² AWG 14 control circuit
    4 mm screw clamp terminal rigid 2 1...6 mm² AWG 10 power circuit
    Screw connector rigid 2 0.5...1 mm² AWG 17 control circuit
    Screw connector flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
    4 mm screw clamp terminal flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
    Screw connector flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
    4 mm screw clamp terminal flexible with cable end 2 1...6 mm² AWG 10 power circuit
    4 mm screw clamp terminal flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
    Screw connector flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
    marking
    CE
    operating position
    Vertical +/- 10 degree
    height
    154 mm
    width
    45 mm
    depth
    131 mm
    product weight
    0.56 kg
    compatibility code
    ATS01N2
    Motor power range AC-3
    7...11 kW at 380...440 V 3 phases
    motor starter type
    Soft starter
    Environment
    electromagnetic compatibility
    Damped oscillating waves level 3 IEC 61000-4-12
    Electrostatic discharge level 3 IEC 61000-4-2
    Immunity to electrical transients level 4 IEC 61000-4-4
    Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
    Voltage/current impulse level 3 IEC 61000-4-5
    Conducted and radiated emissions level B CISPR 11
    Conducted and radiated emissions level B IEC 60947-4-2
    EMC immunity EN 50082-2
    Harmonics IEC 1000-3-2
    Harmonics IEC 1000-3-4
    Immunity to conducted interference caused by radio-electrical fields level 3 IEC 61000-4-6
    Micro-cuts and voltage fluctuation IEC 61000-4-11
    EMC immunity EN 50082-1
    standards
    EN/IEC 60947-4-2
    product certifications
    B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
    CCC
    CSA
    C-Tick
    GOST
    UL
    IP degree of protection
    IP20
    pollution degree
    2 EN/IEC 60947-4-2
    vibration resistance
    1.5 mm peak to peak 3...13 Hz EN/IEC 60068-2-6
    1 gn 13...150 Hz EN/IEC 60068-2-6
    shock resistance
    15 gn 11 ms EN/IEC 60068-2-27
    relative humidity
    5...95 % without condensation or dripping water EN/IEC 60068-2-3
    ambient air temperature for operation
    -10...40 °C without derating
    40...50 °C with current derating of 2 % per °C
    ambient air temperature for storage
    -25...70 °C EN/IEC 60947-4-2
    operating altitude
    <= 1000 m without derating
    > 1000 m with current derating of 2.2 % per additional 100 m
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Russian
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Date 2/2/17
    Size 2 MB
    Date 2/2/17
    Size 2.1 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 6/19/18
    Size 65.4 KB
    Date 9/13/18
    Size 179.8 KB
    Date 4/27/18
    Size 360.8 KB
    Date 5/31/18
    Size 25.6 KB
    Date 6/22/18
    Size 469.4 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Date 8/21/18
    Size 120.2 KB
    End of life manual
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.