I/O output module MES120HNPP -Sepam series 80 NPP- 14 in + 6 out 110...125 V DC

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    module type
    Input/output module
    range of product
    Sepam series 80 NPP
    device short name
    MES120HNPP
    Complementary
    input/output type
    14 inputs + 6 outputs 110...125 V DC
    logic input number
    14 : 110...125 V, limits: 88...150 V DC input current: 3 mA threshold tripping voltage: 82 V enhanced
    number of outputs
    1 control relay output(s)
    5 annunciation relay output(s)
    output type
    Annunciation relay : 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 0.001 kA cos φ > 0.3
    Annunciation relay : 127 V DC continuous current: 2 A breaking capacity: 0.0005 kA L/R < 20 ms
    Annunciation relay : 220 V DC continuous current: 2 A breaking capacity: 0.00015 kA L/R < 20 ms
    Annunciation relay : 24 V DC continuous current: 2 A breaking capacity: 0.002 kA L/R < 20 ms
    Annunciation relay : 250 V DC continuous current: 2 A breaking capacity: 0.0002 kA L/R < 20 ms
    Annunciation relay : 48 V DC continuous current: 2 A breaking capacity: 0.001 kA L/R < 20 ms
    Control relay : 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 0.005 kA cos φ > 0.3 making capacity: < 15 A for 200 ms
    Control relay : 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 0.008 kA resistive making capacity: < 15 A for 200 ms
    Control relay : 127 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R < 40 ms making capacity: < 15 A for 200 ms
    Control relay : 127 V DC continuous current: 8 A breaking capacity: 0.0005 kA L/R < 20 ms making capacity: < 15 A for 200 ms
    Control relay : 127 V DC continuous current: 8 A breaking capacity: 0.0007 kA resistive making capacity: < 15 A for 200 ms
    Control relay : 220 V DC continuous current: 8 A breaking capacity: 0.0001 kA L/R < 40 ms making capacity: < 15 A for 200 ms
    Control relay : 220 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R < 20 ms making capacity: < 15 A for 200 ms
    Control relay : 220 V DC continuous current: 8 A breaking capacity: 0.0003 kA resistive making capacity: < 15 A for 200 ms
    Control relay : 24 V DC continuous current: 8 A breaking capacity: 0.004 kA L/R < 40 ms making capacity: < 15 A for 200 ms
    Control relay : 24 V DC continuous current: 8 A breaking capacity: 0.006 kA L/R < 20 ms making capacity: < 15 A for 200 ms
    Control relay : 24 V DC continuous current: 8 A breaking capacity: 0.008 kA resistive making capacity: < 15 A for 200 ms
    Control relay : 250 V DC continuous current: 8 A breaking capacity: 0.0002 kA resistive making capacity: < 15 A for 200 ms
    Control relay : 48 V DC continuous current: 8 A breaking capacity: 0.001 kA L/R < 40 ms making capacity: < 15 A for 200 ms
    Control relay : 48 V DC continuous current: 8 A breaking capacity: 0.002 kA L/R < 20 ms making capacity: < 15 A for 200 ms
    Control relay : 48 V DC continuous current: 8 A breaking capacity: 0.004 kA resistive making capacity: < 15 A for 200 ms
    height
    170 mm
    width
    40 mm
    depth
    120 mm
    product weight
    0.38 kg
    mechanical robustness
    Earthquakes in operation ( level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
    Earthquakes in operation ( level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
    Jolts de-energized ( level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
    Shocks de-energized ( level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
    Shocks in operation ( level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
    Vibrations de-energized ( level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
    auxiliary connection terminal
    Screw-type connectors 1 cable(s) 1.5 mm²
    Screw-type connectors 1 cable(s) 2.5 mm²
    Screw-type connectors 2 cable(s) 1 mm²
    Screw-type connectors 1 cable(s) 0.2...2.5 mm²
    Screw-type connectors 2 cable(s) 0.2...1 mm²
    Environment
    electromagnetic compatibility
    Fast transient bursts immunity tests-conducted disturbances : IV (4kV, 2.5 kHz ) conforming to IEC 61000-4-4
    Immunity to radiated fields immunity tests-radiated disturbances : III (10 V/m, 80 MHz...2 GHz ) conforming to IEC 61000-4-3
    Fast transient bursts immunity tests-conducted disturbances : A and B (4kV, 2.5 kHz/2 kV, 5 kHz ) conforming to IEC 60255-22-4
    Immunity to conducted RF disturbances immunity tests-conducted disturbances : III (10 V ) conforming to IEC 60255-22-6
    Immunity to magnetic fields at network frequency immunity tests-radiated disturbances : IV (30 A/m (continuous)-300 A/m (1-3 s) ) conforming to IEC 61000-4-8
    Surges immunity tests-conducted disturbances : III (2 kV CM, 1 kV DM ) conforming to IEC 61000-4-5
    1 MHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 1 kV DM ) conforming to IEC 60255-22-1
    1 MHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 2.5 kV DM ) conforming to ANSI C37.90.1
    100 kHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 1 kV DM ) conforming to IEC 61000-4-12
    Conducted disturbance emission emission tests conforming to IEC 60255-25
    Conducted disturbance emission emission tests: A conforming to EN 55022
    Disturbing field emission emission tests conforming to IEC 60255-25
    Disturbing field emission emission tests: A conforming to EN 55022
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 4 kV contact ) conforming to ANSI C37.90.3
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 6 kV contact ) conforming to IEC 60255-22-2
    Fast transient bursts immunity tests-conducted disturbances (4kV, 2.5 kHz ) conforming to ANSI C37.90.1
    Immunity to radiated fields immunity tests-radiated disturbances (10 V/m, 80 MHz...1 GHz ) conforming to IEC 60255-22-3
    Immunity to radiated fields immunity tests-radiated disturbances (35 V/m, 25 MHz...1 GHz ) conforming to ANSI C37.90.2
    Voltage interruptions immunity tests-conducted disturbances (100 % during 100 ms ) conforming to IEC 60255-11
    climatic withstand
    Continuous exposure to damp heat (in operation) : Cab : 10 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
    Continuous exposure to damp heat (in storage) : Cab : 56 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
    Continuous exposure to damp heat (in storage) : Db : 6 days, 95 % RH, 55 °C conforming to IEC 60068-2-30
    Exposure to cold (in operation) : Ad : - 25 °C conforming to IEC 60068-2-1
    Exposure to cold (in storage) : Ab : - 25 °C conforming to IEC 60068-2-1
    Exposure to dry heat (in operation) : Bd : 70 °C conforming to IEC 60068-2-2
    Exposure to dry heat (in storage) : Bb : 70 °C conforming to IEC 60068-2-2
    Salt mist (in operation) : Kb/2 : 6 days conforming to IEC 60068-2-52
    Temperature variation with specified variation rate (in storage) : Nb : - 25 °C to 70 °C, 5 °C/min conforming to IEC 60068-2-14
    Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
    Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068-2-60
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue Sepam serie 20, 40, 60, 80 - Cover (Version 6.0)
    Instruction sheet
    Date
    Size
    Add to My Documents
    Sepam series 80 - Quick Start (Version 04)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.