    GM6

    Gas-Insulated Primary Switchboard up to 40.5 kV

    End-of-Sale Notice

    MV Gas Insulated Switchgear up to 40.5 kV

    GM6
    • Features

      • Indoor Gas Insulated Switchgear (GIS); metal enclosed type switchgear
      • Each functional unit consists of a
      . busbar compartment
      . circuit breaker compartment filled with SF6
      . cable compartment
      . low voltage cabinet
      • Performances:
      . Technology: SF6
      . Standard: IEC
      . Rated voltage: 40.5kV
      . Busbar system: Single / Double
      . Rated current busbar: 4000A
      . Rated operational current: 4000A
      . Rated peak withstand current: 31.5kA
      . Internal Arc Classification: AFLR 25kA/1s - 31.5kA/0.5s
      . Loss of service continuity: NA
      . Partition class: NA

      Benefits

      Safety and continuity of service

      GM6 is designed to meet users’ requirements: space and installation cost savings, operating personnel safetyreliability to ensure a continuous supply of power.
      GM6 is a complete range of standardised functional units which can be easily adapted to fit users' requirements.

      Applications

      GM6 is designed for the medium voltage part of high power substation networks, i.e.

      • Primary HV/MV substations,
      • Intermediate MV/MV substations and
      • HV/MV or MV/MV substations supplying power to manufacturing plants in the heavy industry sector.