Is there a way to store the Lfr setting after power is recycled on the Altivar ATV16?

Published date: 15 November 2018

Issue:
Is there a way to store the Lfr setting after power is recycled on the Altivar ATV16?
 
Product Line:
ATV16
 
Environment:
All
 
Cause:
N/A
 
Resolution: 
You can run the drive in Terminal mode, jumper +10 to AIV and then adjust HSP parameter to control the speed. This will work similar to adjusting Lfr except the value will be stored after power is recycled which can not be done in LFR parameter which reverts back to zero when cycle power.


 