How to perform a factory reset on the ATV320 C suffix drive?

Published date: 15 October 2019

Issue:
How to perform a factory reset on the ATV320 C suffix drive?

Product Line:
Altivar 320

Environment:
All

Cause:
Factory reset.

Resolution:
To perform a factory reset from power up;
Enter on dial.
Scroll down to CONF menu and enter.
Scroll down to FCS- and enter.
Scroll down to FRY- and enter.
Select All so that " mark is at top instead of bottom.
Now go to GFS parameter.
Set it to yes and hold for 2 seconds until it goes back to GFS when you let go.