What is the speed limitation and bandwidth for ethernet backplane

Published date: 11 October 2019

  1. Issue
The speed limitation for X-BUS backplane is 12Mbps and customer would like to know the speed limitation & bandwidth  for Ethernet backplane.
  1. Environment
N/A
  1. Resolution
Ethernet backplane is 100Mbps full duplex. The bandwidth for each slot is as following:
  • Ingress rate limiting must be set to 0.1 Mbps for broadcast traffic.
  • Ingress rate limiting must be set to 1 Mbps for all other traffic.
  • Port egress rate limiting must not be set.
 
  1. FAQ Applicable Conditions 
Any BMEXBP**** backplane
 