Will the display still be active if a ModBus network is attached to the ATS22?

Published date: 04 October 2019

Issue:
Wanting to control, the ATS22, with the Modbus network and also be able to use the remote keypad display. 

Product Line:
ATS22 soft starts

Environment:
Modbus

Cause:
n/a

Resolution:
The ATS22 soft starter has a built in display, as part of the soft starter. The RJ-45 port can be used for a remote mounted display keypad or for Modbus network. If the RJ-45 port is used for communications or for remote keypad the local display on the soft starter control board will still operate. The port can not be used for both a remote keypad and for Modbus communication.

 