How to mitigate the noise or interference on a JR900 trio radio network?

Published date: 26 September 2019

Interference occurs when unwanted radio frequency signals disrupt the use of the JR900 trio radio.
To mitigate the noise or interference on a JR900 trio radio network alter the following radio parameters.
1. Set the hopping interval on a faster rate.
2. Increase the data retransmision parameter.
3. Enable collision avoidance.
4. Enable force retransmissions accross separate hops only when sending critical data on a noisy network.

Note: That adjusting the above will improve network reliability but it make the network more slower.