How do I use/wire the TeSys Island Digital IO module?

Published date: 01 July 2019

Issue:  
How is the TeSys Island IO wired? 

Product Line: 
Tesys Island

Environment:
Digital multifunctional load management solution 
 
Resolution:
  • The digital inputs require an externally supplied 24V signal to drive them high. Simply shorting I0 to IC will not drive the input high.
  • The digital outputs will connect and disconnect an externally supplied 24V source. The 24V is not derived from the island itself, it must be supplied by the user