How to modify runtime security setting on EOTE V3.1 with USB drive

Published date: 08 July 2019

  1. Issue
           How to modify runtime security setting on EOTE V3.1 with USB drive
  1. Environment
           EOTE V3.1
  1. Resolution
  1.  ) Set In the [Project Explorer], select [Security] [Setting], and click [Export].
  2.  ) Define the location and file name.
          Note: To import the exported file to the panel, save the file to the root directory of USB   memory with the specified folder and file name.
                    Folder Name:  UserManagement 
                    File Name: data.bin
       3. )   Enter the encryption key. This key is used for importing and modifying user information.
       4. )   To import user information from the panel, setting up scripts is required.
       5. )   On the screen, touch the import switch.
       6. )   Enter the encryption key. On the panel, the project user information is overwritten.
  1. FAQ Applicable Conditions
           FAQ also applies to Vijeo XD V3.0.
 