EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta

Published date: 21 May 2019

EBO process data from third party LON devices according Device template imported to Building Operation Server.

In case SNVTs types visible in EBO dont match with SNVTs in TAC Vista database after conversion, there must be discrepancy in XIF files which have been imported.

Check Network variabe index numbers for particular SNVTs which do not match after coversion in XIF files.

Correct XIF file manually according LonMark org Technical Resource guide
http;//www.lonmark.org/technical_resources/resource_files/1500/snvt.pdf
 