HOw to write CMD bits 11-15 via Somachine when certain ATV function has assignment for input from SOmachine PLC?

Published date: 15 May 2019

If the ATV is added to a PLC via its ATV DTM then whole command word CMD is managed by Somachine and so fucntion blocks running in SOmachine will not allow to write signle bit of CMD word.
The only solution today is to add device as generic modbus TCP device (not via ATVxxx DTM) and configure I/O scanner manually. Then you can write every single bit of CMD word by your somachine program.