Published date: 20 May 2019

Issue:
ATV320: Wants to set AI2 to current

Product Line:
ATV320


Environment:
Analog input


Cause:
n/a


Resolution:
Checked and AI2 is ONLY for voltage ( 0-10 or 0 to +/-10v). For 4-20ma input, suggest to use AI3, set to current (4-20ma). 
Then go to CTL menu- set Fr1 to AI3
 