How do I program an ATV12 drive to be controlled by the VW3A1106 or VW3A1107 remote keypad?

Published date: 30 April 2019

Issue:
Customer wants to control an ATV12 series drive via the remote keypad VW3A1106 / 1107

Product line:
ATV12

Environment:
All ATV12 models where the VW3A1106 / 1107 keypad will be used.

Cause:
information unavailable in current literature.

Resolution:
Place the drive in local mode by holding the mode button until three LEDs on the left hand side of the display are flashing in sequence, then release the mode button.
Press and hold the ESC button until all three LEDs flash on and off at the same time, then release the ESC button.
Press the enter button and scroll to CONF.
Press Enter then scroll to FULL.
Press Enter then scroll to CTL.
Press Enter then scroll to CHCF.
Press Enter, scroll to SEP
Press Enter then scroll down to CD1.
Press Enter then scroll to LCC.
Press Enter then scroll up to FR1
Press Enter and scroll to LCC.
Press Enter, then press ESC until back to RDY.
Press and hold the ESC button until the LEDs scroll in sequence again.

The drive is now configured for start, stop, and speed control from the keypad.



 