What is the parity on link150 when Modbus ASCII is used?

Published date: 09 April 2019

 
Issue
The user may require parity options on Link150 (EGX150) when transmission mode has been set to Modus ASCII

Product line
Link150

Environment
Link150

Cause

When Modbus ASCII mode is selected, the parity setting is grayed out.


Resolution
The Parity of the serial port is restricted to EVEN when the transmission mode is set to Modbus ASCII. There is no way around changing it to NONE/ODD.