How do I program the ATV630 for +/- speeds via digital inputs?

Published date: 08 April 2019

Issue:
How do I program the ATV630 for reference switching and +/- speeds via digital inputs?

Product Line:
Process Drives

Environment:
ATV630  ATV930

Cause:
Setup +/- speed as second reference. 

Resolution:
[Complete settings] [Command and Reference]
Reference Freq Assign = DIx 
[Ref Freq 2 Config] Fr2 > Configuration reference frequency 2.  > [Ref Frequency via DI]
FR2= +/-  Speed via DI  +speed 
[Complete settings] [Generic functions] [+/- speed]
[+ Speed Assign]  USP  = desired DIx  Increase speed input assignment.
[- Speed Assign]   dSP   = desired DIx  Down speed input assignment.