ATV320 How do I achieve the fastest stop?

Published date: 25 April 2019

Issue:
How do I get the "fastest" possible stop with an ATV320 ?

Product Line:
ATV320

Environment:
All serial numbers

Cause:
Need a fastest stop time.

Resolution: 
With a "beefy" brake resistor that can handle the load. 
Go to Full, then Fun menu:
Ramp: brA ( Dec ramp adapt). set to "no" 

Stt [Type of stop]- Set to Fast stop
Ramp divider ( dcF)- set to 0.