How can I power up an iEM3000 series meters?

Published date: 14 June 2019

Issue

The iEM3000 series meters documentation do not tell how to supply voltage that power up the meter.

Product Line
iEM3000 Series Meters

Environment
iEM3000 series basic metering
 
Cause
To know the maximum voltage to supply, where, and how to wire the supply power.

Resolution
The iEM3000 series meters are powered up throughout the phase voltage connected on V1, V2, V3, and Vn
accordingly to the wiring diagram in the installation guide of the iEM3000 series meter.
The meters support the direct power Voltage (L-L) 3 x 100/173 V AC to 3 x 277/480 V AC (50/60 Hz) and the direct current
measurement up to 63 A or 125 A. Click on this link FA358835 and FA352325 for documentation.