What is the range of motor current (LCR parameter) when read by communication, HMI or Somove?

Published date: 14 March 2019

Lower limit of LCR is of course zero.
The upper limit of LCR is derived from max continuous drive output current in normal duty (ND), to be precise it is 200% of drive rated current.

For example ATV630D11N4 has max continuous output current 23.5A in ND. 
LCR therefore can have value 0 - 47A