Why might I get an NST on my ATV320 when I wire a relay to the digital output (DQ)?

Published date: 07 March 2019

Issue:
Why might I get an NST on my ATV320 when I wire a relay to the digital output (DQ)?

Product Line:
Altivar 320

Environment:
All

Cause:
NST on the ATV320 with relay connected

Resolution:
1. Check to make sure your relay is wired correctly in series with the digital output:
Jumper +24V to DQ+
Wire your + side of your relay coil to DQ-  
Wire the other side of the coil to COM
2. Measure the amperage pull of your relay. The digital output and the drive's +24V supply each have a maximum 100mA capacity. 
If your relay is pulling more than 100mA, it's pulling down the +24V in the drive and causing the NST. 