On PowerTag A9 F63 models, I have problems with the mechanical withstand of voltage picking blade terminals when connecting on a product with wider screw terminals. Is there any recommendation?

Published date: 04 March 2019

The best way to perform the connection of the PowerTag on the product is to place the blade terminal against the fixed part of the product's screw terminal and to align the power wire behind the blade terminal.