Is the P24 and 24V the same?

Published date: 25 March 2019

Issue:
Is there a difference between the P24 and 24V supplies on the ATV930 drives?
 
Product Line:
ATV6xx   ATV9xx
 
Environment:
All serial numbers
 
Cause:
P24 voltage rating
 
Resolution:
Yes, there is a difference.
P24 is a +24Vdc external input supply maximum current: 0.8 A
24V is a +24Vdc output supply for digital and STO safety inputs: maximum 200 mA


 



 