Browse FAQs

What are recommended fuses for DC bus connection on ATV71?

Published date: 26 February 2019

Rating of the fuses is shown in attached file. All fuses are fast-acting fuses (also called high speed fuses, semicondutor fuses, etc.)
THese fuses are dedicated for both DC and AC. In the picture you will find out that rated voltage for the fuses depned on ATV AC supply voltage. For ATV...N4 drive supplied by 400V you need fuses that are rated 690V AC at more.
Search fuses from one of global supliers, like Ferraz, Bussmann, Siba, 

For example when searching 160A fuses for ATV71HD30N4, by looking at
http://www.cooperindustries.com/content/dam/public/bussmann/Electrical/Resources/Catalogs/bus-ele-cat-1007-06-hsf-sq-body.pdf
page  6-31, one example is fuse 170M3014 (160A, 690V, hish speed square-body fuse) or its variant (with indicator, microswitch, etc)
another body style is fuse 
170M1319 (page 6/26) 

Was this helpful?

What can we do to improve the information ?