Why does the OFS diagnostics window show "Assynchronous write2 rejected for group ##TSEventsGroup##"?

Published date: 22 August 2019

Issue
The message Error: Assynchronous write2 rejected for group ##TSEventsGroup## (client #: cliend domain) (uid: #) can show on the OFS log with the customer doesn't follow some best practices.    

Product Line
Vijeo Citect, CitectSCADA, OFS 

Environment
CitectSCADA 2018,  OFS 3.62

Resolution
A reserved OPC group name is to be used at group creation for a TS event porcess and the default name is ##TSEventsGroup##. The OFS can return E_FAIL detected error if one of the operations below are performed:
  • IOPCGroupStateMgt: SetName()
  • IOPCGroupStateMgt: CloneGroup()
  • any OPCSyncIO method
  • any OPCSyncIO2 method
  • write by a nonstandard group
A variable used as TS can't be written, becuase this group is exclusively for subscribe event sources and to operate Synch or Asynch R/W an item must be part exclusively of a "Standard" OPC group. If you see the message below on the OFS log, the first step is to look for write command for TS variables on your SCADA application and remove it. 
"02/02 11:35:01 428ms : Error : Asynchronous write2 rejected for group ##TSEventsGroup## (client 11 : SDSC-SERVERP\Administrator) (uid: 27659)”

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.