What causes a CbF [Circuit Breaker Error] fault on an ATV340 series drive and how do I correct it?

Published date: 11 February 2019

Issue:
Customer is experiencing an CbF fault on an ATV340 series drive.

Product Line:
ATV340

Environment:
Circuit Breaker Logic function is being used.

Cause:
The DC bus voltage level is not correct compared to the circuit breaker logic control (start or stop pulse)
after the configured timeout [Mains V. time out] LCt.

Resolution:
 Verify the circuit breaker logic control (pulse time for start and stop).
 Verify the mechanical state of the circuit breaker.

 